Files
BasicComponents/_Config/IO/Gerät 1 (EtherCAT)/Box 1 (INVEOR_M).xti
2025-11-13 09:19:39 +01:00

72 lines
3.5 KiB
XML

<?xml version="1.0"?>
<TcSmItem xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="http://www.beckhoff.com/schemas/2012/07/TcSmProject" TcSmVersion="1.0" TcVersion="3.1.4026.19" ClassName="CFlbTermDef" SubType="9099">
<ImageDatas>
<ImageData Id="1000">424de6000000000000007600000028000000100000000e000000010004000000000070000000000000000000000000000000000000000000000000008000008000000080800080000000800080008080000080808000c0c0c0000000ff0000ff000000ffff00ff000000ff00ff00ffff0000ffffff0088888888888888888888888888888888fff666ffff6666f8fff6877ff67876fffff7f77ffff67ffffff7f768ff6ffffffff7f78ff67ffffffff7ffff67fffffffff7f78ff67ffffffff7f766fff7fffffff7f77f6fff67fffff6877ff67876ffffffffffffffffffffffffffffffffff</ImageData>
</ImageDatas>
<Box Id="1" BoxType="9099" BoxFlags="#x00000020">
<Name>__FILENAME__</Name>
<ImageId>1000</ImageId>
<EtherCAT SlaveType="2" PdiType="#x0006" StateMBoxPolling="true" UseLrdLwrInsteadOfLrw="true" CycleMBoxPollingTime="0" CoeType="19" FoeType="1" VendorId="#x00000337" ProductCode="#x00000003" RevisionNo="#x00000002" InfoDataAddr="true" PortPhys="17" MaxSlotCount="256" MaxSlotGroupCount="1" SlotPdoIncrement="1" SlotIndexIncrement="16" Type="INVEOR_M" Desc="INVEOR_M">
<SyncMan>001080003600010001000000800080008000001036010000</SyncMan>
<SyncMan>801080003200010002000000800080008000801032010000</SyncMan>
<SyncMan>00111800740001000300000000000001c800001174010000</SyncMan>
<SyncMan>00142800300001000400000000000001c800001430010000</SyncMan>
<Fmmu>0000000000000000001100020100000001000000000000000000000000000000</Fmmu>
<Fmmu>0000000000000000001400010100000002000000000000000000000000000000</Fmmu>
<Fmmu>00000000000000000d0800010100000003000000000000000000000000000000</Fmmu>
<Pdo Name="Inputs0" Index="#x1a00" Flags="#x0000" SyncMan="3">
<Entry Name="Statuswort" Index="#x3000" Sub="#x01">
<Type>UDINT</Type>
</Entry>
<Entry Name="Istfrequenz" Index="#x3000" Sub="#x02">
<Type>REAL</Type>
</Entry>
<Entry Name="Motorspannung" Index="#x3000" Sub="#x03">
<Type>REAL</Type>
</Entry>
<Entry Name="Motorstrom" Index="#x3000" Sub="#x04">
<Type>REAL</Type>
</Entry>
<Entry Name="Netzspannung" Index="#x3000" Sub="#x05">
<Type>REAL</Type>
</Entry>
<Entry Name="Frequenzsollwert" Index="#x3000" Sub="#x06">
<Type>REAL</Type>
</Entry>
<Entry Name="Digitaleingänge bitcodiert" Index="#x3000" Sub="#x07">
<Type>UDINT</Type>
</Entry>
<Entry Name="Analogeingang 1" Index="#x3000" Sub="#x08">
<Type>REAL</Type>
</Entry>
<Entry Name="Fehlerwort 1" Index="#x3000" Sub="#x09">
<Type>UDINT</Type>
</Entry>
<Entry Name="Fehlerwort 2" Index="#x3000" Sub="#x0a">
<Type>UDINT</Type>
</Entry>
</Pdo>
<Pdo Name="Outputs0" Index="#x1600" InOut="1" Flags="#x0000" SyncMan="2">
<Entry Name="Steuerwort" Index="#x2000" Sub="#x01">
<Type>UDINT</Type>
</Entry>
<Entry Name="Sollfrequenz" Index="#x2000" Sub="#x02">
<Type>REAL</Type>
</Entry>
<Entry Name="Digitalausgänge / Relais" Index="#x2000" Sub="#x03">
<Type>UDINT</Type>
</Entry>
<Entry Name="Analogausgang 1" Index="#x2000" Sub="#x04">
<Type>REAL</Type>
</Entry>
<Entry Name="Kundenspez.SPS Eingangsgröße 1 (Digital 32Bit)" Index="#x2000" Sub="#x05">
<Type>UDINT</Type>
</Entry>
<Entry Name="Kundenspez.SPS Eingangsgröße 1 (Digital 32Bit)" Index="#x2000" Sub="#x06">
<Type>UDINT</Type>
</Entry>
</Pdo>
</EtherCAT>
</Box>
</TcSmItem>