Added error and waring messages and updated tower light inputs
- Added strings not ready in time error - Added battery already full warning - Added battery already empty warning - Added battery in stop input to tower light - Added warnings active to tower light - Added BMS State Machine errors to tower light input
This commit is contained in:
@@ -474,6 +474,7 @@ CASE _iState OF
|
||||
|
||||
IF (NOT xEnable) THEN
|
||||
_xEnable := FALSE;
|
||||
_xReleaseLimitErrorsInternal := FALSE;
|
||||
_iState := 0;
|
||||
END_IF
|
||||
|
||||
@@ -516,6 +517,7 @@ CASE _iState OF
|
||||
_tonSafetyOkTimeout.IN := FALSE;
|
||||
xResetSafety := FALSE;
|
||||
_xEnable := FALSE;
|
||||
_xReleaseLimitErrorsInternal := FALSE;
|
||||
_iState := 40;
|
||||
END_IF
|
||||
|
||||
@@ -580,6 +582,7 @@ CASE _iState OF
|
||||
IF (NOT xEnable) THEN
|
||||
_tonSafetyOkTimeout.IN := FALSE;
|
||||
_xEnable := FALSE;
|
||||
_xReleaseLimitErrorsInternal := FALSE;
|
||||
//eStatus := E_COMPONENT_STATUS.SHUTDOWN;
|
||||
_iState := 40;
|
||||
END_IF
|
||||
@@ -663,11 +666,11 @@ CASE _iState OF
|
||||
// Shutdown
|
||||
IF (NOT xEnable) THEN
|
||||
_xEnable := FALSE;
|
||||
_xReleaseLimitErrorsInternal := FALSE;
|
||||
IF GVL_CONFIG.xShutdownDischargeWithInverter THEN
|
||||
_rPowerInverterInternal := GVL_CONFIG.rAbsShutdownDischargePower;
|
||||
_iState := 31;
|
||||
ELSE
|
||||
_xReleaseLimitErrorsInternal := FALSE;
|
||||
_rPowerInverterInternal := 0.0;
|
||||
_xEnableInverter := FALSE;
|
||||
_iState := 40;
|
||||
@@ -675,7 +678,6 @@ CASE _iState OF
|
||||
|
||||
ELSIF (NOT _xAllModulesReady) OR (NOT _xBalanceOk) OR (NOT xSafetyIntlksOk) OR (NOT xRepairSwitchOk) OR (_xErrorInternal) THEN
|
||||
xError := TRUE;
|
||||
_xReleaseLimitErrorsInternal := FALSE;
|
||||
_xEnable := FALSE;
|
||||
_rPowerInverterInternal := 0.0;
|
||||
_xEnableInverter := FALSE;
|
||||
|
||||
@@ -70,6 +70,15 @@ VAR
|
||||
// NA Protection Alarm
|
||||
_fbNAProtectionAlarm : FB_TcAlarm;
|
||||
|
||||
// String ready timeout alarm
|
||||
_fbStringReadyTimeoutAlarm : FB_AlarmMessage;
|
||||
|
||||
// Battery already full warning
|
||||
_fbBatteryAlreadyFullWarning : FB_AlarmMessage;
|
||||
|
||||
// Battery already empty warning
|
||||
_fbBatteryAlreadyEmptyWarning : FB_AlarmMessage;
|
||||
|
||||
// First cycle tag
|
||||
_xFirstCycle : BOOL := TRUE;
|
||||
|
||||
@@ -120,6 +129,7 @@ VAR
|
||||
|
||||
_xErrorActive : BOOL;
|
||||
_xWarningActive : BOOL;
|
||||
_xBatteryActive : BOOL;
|
||||
|
||||
// Battery in safety check mode
|
||||
_xInSafetyCheckMode : BOOL;
|
||||
@@ -149,6 +159,7 @@ VAR
|
||||
// Hardware reset button rising edge trigger
|
||||
_fbRTrigHardwareAck : R_TRIG;
|
||||
|
||||
// String not ready in time timeout
|
||||
_fbStringReadyTimeout : TON;
|
||||
|
||||
// Sum of voltage of all active strings
|
||||
@@ -176,6 +187,9 @@ VAR
|
||||
_xStringsInAutoMode : BOOL;
|
||||
_xStringSafetyComError : BOOL;
|
||||
|
||||
_xStringNotReadyInTime : BOOL;
|
||||
_xErrorBMSSMActive : BOOL;
|
||||
|
||||
_eStringOpMode : E_STRING_OPERATING_MODE;
|
||||
|
||||
_rMaxCurrentInverterDCVoltage : REAL;
|
||||
@@ -227,6 +241,10 @@ END_VAR
|
||||
_fbEMSHeartbeatAlarm.CreateEx(stEventEntry := TC_EVENTS.BMSEvents.EMSHeartbeatTimeout, TRUE, 0);
|
||||
|
||||
_fbNAProtectionAlarm.CreateEx(stEventEntry := TC_EVENTS.BMSEvents.NAProtectionTripped, TRUE, 0);
|
||||
|
||||
_fbStringReadyTimeoutAlarm.Init(stEventType := TC_EVENTS.BMSEvents.StringReadyTimeout, TRUE);
|
||||
_fbBatteryAlreadyFullWarning.Init(stEventType := TC_EVENTS.BMSEvents.BatteryAlreadyFull, FALSE);
|
||||
_fbBatteryAlreadyEmptyWarning.Init(stEventType := TC_EVENTS.BMSEvents.BatteryAlreadyEmpty, FALSE);
|
||||
END_IF
|
||||
|
||||
// Reset error flag
|
||||
@@ -518,7 +536,7 @@ IF _fbTempCabinetSCSString2.xError THEN
|
||||
_xErrorActive := TRUE;
|
||||
END_IF
|
||||
|
||||
// Handle string 1 modbus error and warning
|
||||
// Handle string 2 modbus error and warning
|
||||
GVL_MODBUS.stBMSErrorReg.wStringErrorActive.1 := _afbStrings[1].xError;
|
||||
GVL_MODBUS.stBMSErrorReg.wStringWarningActive.1 := _afbStrings[1].xWarning;
|
||||
GVL_MODBUS.stBMSErrorReg.wString2ErrorActive.stBitmap.bDCSwitch := (NOT _afbStrings[1].xRepairSwitchOk);
|
||||
@@ -528,9 +546,6 @@ GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bTCabinetString2Module2High
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bTCabinetString2Module3High := _afbStrings[1].xTempCabinetModule3Warning;
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bTCabinetSCSString2High := _fbTempCabinetSCSString2.xWarningHigh;
|
||||
|
||||
// Copy general error to modbus error register
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSErrorActive.stBitmap.bError := _xErrorActive;
|
||||
|
||||
|
||||
// ===============================
|
||||
// Get global string status information
|
||||
@@ -950,6 +965,10 @@ IF _xGetPowerMeterData THEN
|
||||
END_IF
|
||||
|
||||
|
||||
// Handle modbus global warning and error flag
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSErrorActive.stBitmap.bError := _xErrorActive OR _xErrorBMSSMActive;
|
||||
|
||||
|
||||
// Call safety fb
|
||||
_fbSafety(refuStringErrorsModbus := GVL_MODBUS.stBMSErrorReg.wBMSErrorActive);
|
||||
|
||||
@@ -971,6 +990,7 @@ END_IF
|
||||
|
||||
// Reset alarm confirmation
|
||||
IF _xConfirmAlarms OR _rtHardwareResetButton.Q THEN
|
||||
_xErrorBMSSMActive := FALSE;
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSErrorActive.wRegister := 0;
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.wRegister := 0;
|
||||
GVL_MODBUS.stBMSErrorReg.wString1ErrorActive.wRegister := 0;
|
||||
@@ -981,10 +1001,10 @@ END_IF
|
||||
_fbPowerMeter24V();
|
||||
|
||||
_fbTowerLight(
|
||||
xAutoInStop := FALSE,
|
||||
xWarningActive := FALSE,
|
||||
xAutoInStop := NOT _xBatteryActive,
|
||||
xWarningActive := _xWarningActive,
|
||||
xWarningConfirmPending := FALSE,
|
||||
xErrorActive := _xErrorActive,
|
||||
xErrorActive := _xErrorActive OR _xErrorBMSSMActive,
|
||||
xErrorConfirmPending := FALSE);]]></ST>
|
||||
</Implementation>
|
||||
<Action Name="SM_AUTO" Id="{b5166e16-4fea-442b-9560-02c156f9a9ad}">
|
||||
@@ -1025,6 +1045,7 @@ _fbTowerLight(
|
||||
IF _xStringsReady AND (NOT _xStringsErrorActive) THEN
|
||||
_xGetPowerMeterData := TRUE;
|
||||
_fbStringReadyTimeout(IN := FALSE);
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSErrorActive.stBitmap.bStringsNotReadyInTime := 1;
|
||||
_rPowerInverter := 0.0;
|
||||
// Set active parallel members (modbus)
|
||||
GVL_MODBUS.stModbusEMSComm.stModbusReg10.uiActiveParallelMembers := GVL_CONFIG.uiNumberOfStrings;
|
||||
@@ -1034,10 +1055,11 @@ _fbTowerLight(
|
||||
|
||||
IF _xStringsErrorActive OR _fbStringReadyTimeout.Q THEN
|
||||
_fbStringReadyTimeout(IN := FALSE);
|
||||
_xStringNotReadyInTime := TRUE;
|
||||
_xEnableString := FALSE;
|
||||
GVL_SCADA.stAutomaticModeHMI.diSetpointAutomatic := 0;
|
||||
_xCanChangeMode := TRUE;
|
||||
_iState := 45;
|
||||
_iState := 1000;
|
||||
END_IF
|
||||
|
||||
|
||||
@@ -1053,6 +1075,7 @@ _fbTowerLight(
|
||||
// Set inverter power to modbus requested power
|
||||
_rPowerInverter := _rAutoPowerRequest;
|
||||
_xReleaseInverterPower := TRUE;
|
||||
_xBatteryActive := TRUE;
|
||||
|
||||
// Check if the battery should still be active
|
||||
IF (_rAutoPowerRequest = 0.0) AND NOT GVL_MODBUS.stModbusEMSComm.stModbusReg12.wBMSControlsRegister.stBitmap.bScheduleActive THEN
|
||||
@@ -1172,6 +1195,7 @@ _fbTowerLight(
|
||||
IF GVL_CONFIG.xShutdownDischargeWithInverter THEN
|
||||
_iState := 40;
|
||||
ELSE
|
||||
_xBatteryActive := FALSE;
|
||||
_xReleaseInverterPower := FALSE;
|
||||
_rPowerInverter := 0.0;
|
||||
_xEnableString := FALSE;
|
||||
@@ -1193,6 +1217,7 @@ _fbTowerLight(
|
||||
IF _xStringsShutdownDischargeAllowed OR _xEMSHeartbeatNotOK THEN
|
||||
_rPowerInverter := GVL_CONFIG.rAbsShutdownDischargePower;
|
||||
ELSE
|
||||
_xBatteryActive := FALSE;
|
||||
_xReleaseInverterPower := FALSE;
|
||||
_xGetPowerMeterData := TRUE;
|
||||
GVL_MODBUS.stModbusEMSComm.stModbusReg10.uiActiveParallelMembers := 0;
|
||||
@@ -1213,12 +1238,10 @@ _fbTowerLight(
|
||||
IF (ABS(_rAutoPowerRequest) > DINT_TO_REAL(GVL_CONFIG.diMinimumAbsPowerForEnable)) AND (NOT _xStringsErrorActive) AND _xStringsAllInAutomaticMode THEN
|
||||
IF _rAutoPowerRequest < 0 AND GVL_MODBUS.stModbusEMSComm.stModbusReg11.eChargeStatus <> E_CHARGE_STATUS.FULL THEN
|
||||
_iState := 0;
|
||||
// TODO: Meldung ausgeben, dass Batterie schon voll ist
|
||||
END_IF
|
||||
|
||||
IF _rAutoPowerRequest > 0 AND GVL_MODBUS.stModbusEMSComm.stModbusReg11.eChargeStatus <> E_CHARGE_STATUS.EMPTY THEN
|
||||
_iState := 0;
|
||||
// TODO: Meldung ausgeben, dass Batterie schon leer ist.
|
||||
END_IF
|
||||
END_IF
|
||||
|
||||
@@ -1236,12 +1259,10 @@ _fbTowerLight(
|
||||
_xCanChangeMode := FALSE;
|
||||
IF (_rAutoPowerRequest < 0 OR GVL_MODBUS.stModbusEMSComm.stModbusReg12.wBMSControlsRegister.stBitmap.bScheduleActive) AND GVL_MODBUS.stModbusEMSComm.stModbusReg11.eChargeStatus <> E_CHARGE_STATUS.FULL THEN
|
||||
_iState := 0;
|
||||
// TODO: Meldung ausgeben, dass Batterie schon voll ist
|
||||
END_IF
|
||||
|
||||
IF (_rAutoPowerRequest > 0 OR GVL_MODBUS.stModbusEMSComm.stModbusReg12.wBMSControlsRegister.stBitmap.bScheduleActive) AND GVL_MODBUS.stModbusEMSComm.stModbusReg11.eChargeStatus <> E_CHARGE_STATUS.EMPTY THEN
|
||||
_iState := 0;
|
||||
// TODO: Meldung ausgeben, dass Batterie schon leer ist.
|
||||
END_IF
|
||||
|
||||
IF (_rAutoPowerRequest <> 0 OR GVL_MODBUS.stModbusEMSComm.stModbusReg12.wBMSControlsRegister.stBitmap.bScheduleActive) THEN
|
||||
@@ -1263,8 +1284,11 @@ _fbTowerLight(
|
||||
GVL_MODBUS.stModbusEMSComm.stModbusReg10.uiActiveParallelMembers := 0;
|
||||
_xReleaseInverterPower := FALSE;
|
||||
_xEnableString := FALSE;
|
||||
_xBatteryActive := FALSE;
|
||||
_rPowerInverter := 0.0;
|
||||
GVL_MODBUS.stModbusEMSComm.stModbusReg11.eBatteryStatus := E_BATTERY_STATUS.ERROR;
|
||||
_xErrorBMSSMActive := TRUE;
|
||||
_xStringNotReadyInTime := FALSE;
|
||||
_iState := 1010;
|
||||
|
||||
1010: // Wait for reset from error state
|
||||
@@ -1285,6 +1309,32 @@ _fbTowerLight(
|
||||
END_IF
|
||||
END_CASE
|
||||
|
||||
// String not ready in time alarm
|
||||
_fbStringReadyTimeoutAlarm(xActive := _xStringNotReadyInTime , xAcknowledge := _xConfirmAlarms);
|
||||
IF GVL_MODBUS.stBMSErrorReg.wBMSErrorActive.stBitmap.bStringsNotReadyInTime AND _fbStringReadyTimeoutAlarm.ClearedAndConfirmed THEN
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSErrorActive.stBitmap.bStringsNotReadyInTime := 0;
|
||||
END_IF
|
||||
|
||||
// Battery already full warning
|
||||
IF (_rAutoPowerRequest < 0) AND GVL_MODBUS.stModbusEMSComm.stModbusReg11.eChargeStatus = E_CHARGE_STATUS.FULL THEN
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bBatteryAlreadyFull := 1;
|
||||
_fbBatteryAlreadyFullWarning(xActive := TRUE);
|
||||
_xWarningActive := TRUE;
|
||||
ELSE
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bBatteryAlreadyFull := 0;
|
||||
_fbBatteryAlreadyFullWarning(xActive := FALSE);
|
||||
END_IF
|
||||
|
||||
// Battery already empty
|
||||
IF (_rAutoPowerRequest > 0) AND GVL_MODBUS.stModbusEMSComm.stModbusReg11.eChargeStatus = E_CHARGE_STATUS.EMPTY THEN
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bBatteryAlreadyEmpty := 1;
|
||||
_fbBatteryAlreadyEmptyWarning(xActive := TRUE);
|
||||
_xWarningActive := TRUE;
|
||||
ELSE
|
||||
GVL_MODBUS.stBMSErrorReg.wBMSWarningActive.stBitmap.bBatteryAlreadyEmpty := 0;
|
||||
_fbBatteryAlreadyEmptyWarning(xActive := FALSE);
|
||||
END_IF
|
||||
|
||||
// Calculate string power balancing
|
||||
IF _rStringsSumVoltage <> 0 AND (_uiNumberOfActiveStrings <> 0) THEN
|
||||
FOR _ui := 0 TO (GVL_CONFIG.uiNumberOfStrings-1) DO
|
||||
|
||||
62
PLC/POUs/Utility/FB_AlarmMessage.TcPOU
Normal file
62
PLC/POUs/Utility/FB_AlarmMessage.TcPOU
Normal file
@@ -0,0 +1,62 @@
|
||||
<?xml version="1.0" encoding="utf-8"?>
|
||||
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.12">
|
||||
<POU Name="FB_AlarmMessage" Id="{4e628f13-10b9-47d9-8d26-ceb4bcb9bf43}" SpecialFunc="None">
|
||||
<Declaration><![CDATA[FUNCTION_BLOCK FB_AlarmMessage
|
||||
VAR_INPUT
|
||||
xActive : BOOL;
|
||||
xAcknowledge : BOOL;
|
||||
END_VAR
|
||||
VAR_OUTPUT
|
||||
END_VAR
|
||||
VAR
|
||||
_fbAlarmMessage : Fb_TcAlarm;
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[IF xActive AND (NOT _fbAlarmMessage.bRaised) THEN
|
||||
_fbAlarmMessage.Raise();
|
||||
END_IF
|
||||
|
||||
IF (NOT xActive) AND (_fbAlarmMessage.bRaised) THEN
|
||||
_fbAlarmMessage.Clear(0);
|
||||
END_IF
|
||||
|
||||
IF _fbAlarmMessage.eConfirmationState = TcEventConfirmationState.WaitForConfirmation AND xAcknowledge THEN
|
||||
_fbAlarmMessage.Confirm(0);
|
||||
END_IF]]></ST>
|
||||
</Implementation>
|
||||
<Property Name="Arguments" Id="{f40c819a-ad71-4e81-830e-67d02b4e9e2f}">
|
||||
<Declaration><![CDATA[PROPERTY PUBLIC Arguments : I_TcArguments]]></Declaration>
|
||||
<Get Name="Get" Id="{c1b8ca1b-cb6c-4841-8282-61423914cb4e}">
|
||||
<Declaration><![CDATA[VAR
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[Arguments := _fbAlarmMessage.ipArguments;]]></ST>
|
||||
</Implementation>
|
||||
</Get>
|
||||
</Property>
|
||||
<Property Name="ClearedAndConfirmed" Id="{4e7fa79e-e44f-42ff-ab45-0e14a9921a12}">
|
||||
<Declaration><![CDATA[PROPERTY ClearedAndConfirmed : BOOL]]></Declaration>
|
||||
<Get Name="Get" Id="{70df159d-fc9d-44c5-ae42-7d731a5dae12}">
|
||||
<Declaration><![CDATA[VAR
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[ClearedAndConfirmed := (NOT _fbAlarmMessage.bRaised) AND (_fbAlarmMessage.eConfirmationState <> TcEventConfirmationState.WaitForConfirmation);]]></ST>
|
||||
</Implementation>
|
||||
</Get>
|
||||
</Property>
|
||||
<Method Name="Init" Id="{c066689c-dd69-4f09-b5b0-76b34267abac}">
|
||||
<Declaration><![CDATA[METHOD Init : BOOL
|
||||
VAR_INPUT
|
||||
stEventType : TcEventEntry;
|
||||
xWithConfirmation : BOOL;
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[_fbAlarmMessage.CreateEx(stEventEntry := stEventType, bWithConfirmation := xWithConfirmation);]]></ST>
|
||||
</Implementation>
|
||||
</Method>
|
||||
</POU>
|
||||