<?xml version="1.0" encoding="utf-8"?>
|
|
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.8">
|
|
<POU Name="FB_Unit" Id="{e9bb815b-eb46-4920-800d-910484e58b22}" SpecialFunc="None">
|
|
<Declaration><![CDATA[FUNCTION_BLOCK FB_Unit
|
|
VAR_INPUT
|
|
// Unit configuration
|
|
stUnitConfig : REFERENCE TO ST_UNIT_CONFIG;
|
|
|
|
// HMI interface
|
|
stHMIInterface : REFERENCE TO ST_UNIT_HMI_INTERFACE;
|
|
|
|
// Components shortage workaround
|
|
// xVoltageSensorIs1500V : BOOL;
|
|
|
|
// Start unit
|
|
xEnable : BOOL;
|
|
|
|
// Star balancing
|
|
xStartBalancing : BOOL;
|
|
|
|
// Unit in safety check mode
|
|
xInSafetyCheckMode : BOOL;
|
|
|
|
// Emergency stop ok
|
|
xEmergencyStopOk : BOOL;
|
|
|
|
// All safetyinterlocks are ok
|
|
xSafetyIntlksOk : BOOL;
|
|
|
|
// Release alarms
|
|
xReleaseErrors : BOOL;
|
|
|
|
// Release analog io limit errors
|
|
xReleaseLimitErrors : BOOL;
|
|
|
|
// Release manual mode
|
|
xReleaseManualMode : BOOL;
|
|
|
|
// Input to confirm all errors
|
|
xConfirmAlarms : BOOL;
|
|
|
|
// Balancing target Voltage
|
|
rBalancingTargetVoltage : REAL;
|
|
|
|
// Switch all components to manual mode
|
|
xAllToManualMode : BOOL;
|
|
|
|
// Inverter enabled status
|
|
xInverterEnabled : BOOL;
|
|
END_VAR
|
|
VAR_OUTPUT
|
|
// Unit state
|
|
//eUnitState : E_COMPONENT_STATUS := E_COMPONENT_STATUS.OFF;
|
|
|
|
// Unit ready
|
|
xReady : BOOL;
|
|
|
|
// Unit completely off
|
|
xOff : BOOL := TRUE;
|
|
|
|
// Unit can be discharged during shutdown sequence
|
|
xShutdownDischargeAllowed : BOOL;
|
|
|
|
// Unit in shutdown segment discharge mode
|
|
xInShutdownDischargeMode : BOOL;
|
|
|
|
// Error active
|
|
xError : BOOL;
|
|
|
|
// Warning active
|
|
xWarning : BOOL;
|
|
|
|
// Current Unit voltage
|
|
rCurrentVoltage : REAL;
|
|
|
|
// All components in automatic mode
|
|
xAllComponentsInAuto : BOOL;
|
|
|
|
// Balancing done
|
|
xBalancingDone : BOOL;
|
|
|
|
// Reset MCB
|
|
xResetMCB AT %Q* : BOOL;
|
|
END_VAR
|
|
VAR
|
|
// Check unit condition after some time during startup
|
|
_timUnitStartupWaitTime : TIME := T#1M;
|
|
|
|
// Valves posolyt
|
|
_fbPosolytValveTankOutlet : FB_Valve(CONCAT(_sName, ' - Posolyt tank outlet'));
|
|
|
|
// Valves negolyt
|
|
_fbNegolytValveTankOutlet : FB_Valve(CONCAT(_sName, ' - Negolyt tank outlet'));
|
|
|
|
// Pumps posolyt
|
|
_fbPosolytPumpInlet : FB_MotorAnalog(CONCAT(_sName, ' - Posolyt segment inlet'));
|
|
|
|
// Pumps negolyt
|
|
_fbNegolytPumpInlet : FB_MotorAnalog(CONCAT(_sName, ' - Negolyt segment inlet'));
|
|
|
|
// Pressure sensors posolyt
|
|
_fbPressurePosolytSegmentInlet : FB_AnalogInput(CONCAT(_sName, ' - P1_P'));
|
|
_fbPressurePosolytTankInlet : FB_AnalogInput(CONCAT(_sName, ' - P3_P'));
|
|
|
|
// Pressure sensors negolyt
|
|
_fbPressureNegolytSegmentInlet : FB_AnalogInput(CONCAT(_sName, ' - P1_N'));
|
|
_fbPressureNegolytTankInlet : FB_AnalogInput(CONCAT(_sName, ' - P3_N'));
|
|
|
|
// Temperature sensor posolyt
|
|
_fbTempSensorPosolyt : FB_AnalogInput(CONCAT(Name, ' - T1_P'));
|
|
|
|
// Temperature sensor negolyt
|
|
_fbTempSensorNegolyt : FB_AnalogInput(CONCAT(Name, ' - T1_N'));
|
|
|
|
// Unit voltage
|
|
_fbVoltageSegment : FB_AnalogInput('Voltage');
|
|
|
|
// Valve posolyt tank outlet interlocks
|
|
_stPosolytValveTankOutletPIntlk : T_INTERLOCK;
|
|
_stPosolytValveTankOutletPIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0000;
|
|
|
|
_stPosolytValveTankOutletSIntlk : T_INTERLOCK;
|
|
_stPosolytValveTankOutletSIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0001;
|
|
|
|
// Valve negolyt tank outlet interlocks
|
|
_stNegolytValveTankOutletPIntlk : T_INTERLOCK;
|
|
_stNegolytValveTankOutletPIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0000;
|
|
|
|
_stNegolytValveTankOutletSIntlk : T_INTERLOCK;
|
|
_stNegolytValveTankOutletSIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0001;
|
|
|
|
// Pump posolyt inlet interlocks
|
|
_stPosolytPumpInletPIntlk : T_INTERLOCK;
|
|
_stPosolytPumpInletPIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0001;
|
|
_stPosolytPumpInletSIntlk : T_INTERLOCK;
|
|
_stPosolytPumpInletSIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0001;
|
|
|
|
// Pump negolyt inlet interlocks
|
|
_stNegolytPumpInletPIntlk : T_INTERLOCK;
|
|
_stNegolytPumpInletPIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0001;
|
|
_stNegolytPumpInletSIntlk : T_INTERLOCK;
|
|
_stNegolytPumpInletSIntlkUsed : T_INTERLOCK := 2#0000_0000_0000_0001;
|
|
|
|
// Error active
|
|
_xErrorActive : BOOL;
|
|
|
|
// Warning active
|
|
_xWarningActive : BOOL;
|
|
|
|
// Shutdown discharge allowed voltage
|
|
_rShutdownDischargeVoltageThreshold : REAL;
|
|
|
|
// Current state
|
|
_iState: INT;
|
|
|
|
// All components in automatic mode
|
|
_xAllComponentsInAutomatic : BOOL;
|
|
|
|
// Not all components in automatic mode alarm
|
|
_fbNotAllAutomaticAlarm : FB_TcAlarm;
|
|
|
|
// Pressure difference between pos and neg inlet to big
|
|
_fbPressureDiffToBig : FB_TcAlarm;
|
|
|
|
// General unit error
|
|
_fbUnitError : FB_TcAlarm;
|
|
|
|
// Unit name
|
|
_sName : STRING;
|
|
|
|
// Unit startup check timer
|
|
_tonStartupCheck : TON;
|
|
|
|
// Enable voltage limit checks
|
|
_xEnableVoltageLimitChecks : BOOL;
|
|
|
|
// Manual mode allowed flag
|
|
_xReleaseManualMode : BOOL;
|
|
|
|
_xReleaseSignalDeltaPSegment : FB_ReleaseSignal;
|
|
_xDeltaPSegmentInletToHigh : BOOL;
|
|
_xEnableCheckForDeltaPSegmentInlet : BOOL;
|
|
_xErrorDeltaPSegmentInlet : BOOL;
|
|
|
|
// Setpoint posolyt pump inlet
|
|
_rSetpointPosolytPumpInlet : REAL;
|
|
|
|
// Setpoint negolyt pump inlet
|
|
_rSetpointNegolytPumpInlet : REAL;
|
|
|
|
// Timer for resetting the MCB (minimum on time 0,5s)
|
|
_tofResetMCB : TOF := (PT := T#0.75S);
|
|
|
|
// Timeout Voltage not reached
|
|
_tonVoltageCheckTimeput : TON := (PT := T#2M);
|
|
|
|
// Freezed balancing target voltage
|
|
_rBalancingTargetVoltage : REAL;
|
|
|
|
// Trigger for switching to manual mode
|
|
_rtrigSwitchToManualMode : R_TRIG;
|
|
|
|
// Trigger for switching to automatic mode
|
|
_rtrigSwitchToAutoMode : R_TRIG;
|
|
_tonManualMode : TON;
|
|
|
|
// Filtered pressure sensor posolyt segment inlet data for HMI
|
|
_rFilteredPressPosolytInlet : REAL;
|
|
|
|
// Filtered pressure sensor posolyt segment inlet data for HMI
|
|
_rFilteredPressNegolytInlet : REAL;
|
|
|
|
// Filtered pressure sensor posolyt tank inlet data for HMI
|
|
_rFilteredPressPosolytTank : REAL;
|
|
|
|
// Filtered pressure sensor posolyt tank inlet data for HMI
|
|
_rFilteredPressNegolytTank : REAL;
|
|
|
|
// Pumps ready
|
|
_xPumpsReady : BOOL;
|
|
|
|
// Indicate if it ise the first cycle
|
|
xFirstCycle : BOOL := TRUE;
|
|
END_VAR
|
|
]]></Declaration>
|
|
<Implementation>
|
|
<ST><![CDATA[IF xFirstCycle THEN
|
|
_fbPosolytValveTankOutlet.Name := CONCAT(_sName, ' - Posolyt tank outlet');
|
|
stHMIInterface.stNS12.sName := 'Posolyt tank outlet';
|
|
|
|
_fbNegolytValveTankOutlet.Name := CONCAT(_sName, ' - Negolyt tank outlet');
|
|
stHMIInterface.stNS22.sName := 'Negolyt tank outlet';
|
|
|
|
_fbPosolytPumpInlet.Name := CONCAT(_sName, ' - Posolyt segment inlet');
|
|
stHMIInterface.stNS11.sName := 'Posolyt segment inlet';
|
|
|
|
_fbNegolytPumpInlet.Name := CONCAT(_sName, ' - Negolyt segment inlet');
|
|
stHMIInterface.stNS21.sName := 'Negolyt segment inlet';
|
|
|
|
_fbPressurePosolytSegmentInlet.Name := CONCAT(_sName, ' - Pressure Posolyt Segment Inlet');
|
|
_fbPressurePosolytTankInlet.Name := CONCAT(_sName, ' - Pressure Posolyt Tank inlet');
|
|
|
|
_fbPressureNegolytSegmentInlet.Name := CONCAT(_sName, ' - Pressure Negolyt Segment Inlet');
|
|
_fbPressureNegolytTankInlet.Name := CONCAT(_sName, ' - Pressure Negolyt Tank Inlet');
|
|
|
|
_fbTempSensorPosolyt.Name := CONCAT(_sName, ' - Temperature Posolyt Tank Inlet');
|
|
_fbTempSensorNegolyt.Name := CONCAT(_sName, ' - Temperature Negolyt Tank Inlet');
|
|
|
|
_fbVoltageSegment.Name := CONCAT(_sName, ' - Voltage');
|
|
|
|
_fbUnitError.ipArguments.Clear().AddString(_sName);
|
|
|
|
_fbPressureDiffToBig.CreateEx(stEventEntry := TC_EVENTS.General.PressureDiffToBig, TRUE, 0);
|
|
_fbPressureDiffToBig.ipArguments.Clear().AddString(_sName);
|
|
|
|
xFirstCycle := FALSE;
|
|
END_IF
|
|
|
|
|
|
// Manual mode trigger
|
|
_tonManualMode(IN := (xAllToManualMode AND xReleaseManualMode), PT := T#10S);
|
|
_rtrigSwitchToManualMode(CLK := _tonManualMode.Q);
|
|
IF _rtrigSwitchToManualMode.Q THEN
|
|
_fbPosolytValveTankOutlet.ReqManualMode();
|
|
_fbNegolytValveTankOutlet.ReqManualMode();
|
|
_fbPosolytPumpInlet.ReqManualMode();
|
|
_fbNegolytPumpInlet.ReqManualMode();
|
|
END_IF
|
|
|
|
// Auto mode trigger
|
|
_rtrigSwitchToAutoMode(CLK := (NOT _tonManualMode.Q));
|
|
IF _rtrigSwitchToAutoMode.Q THEN
|
|
_fbPosolytValveTankOutlet.ReqAutomaticMode();
|
|
_fbNegolytValveTankOutlet.ReqAutomaticMode();
|
|
_fbPosolytPumpInlet.ReqAutomaticMode();
|
|
_fbNegolytPumpInlet.ReqAutomaticMode();
|
|
END_IF
|
|
|
|
// Reset MCB logic
|
|
_tofResetMCB(IN := xConfirmAlarms);
|
|
xResetMCB := _tofResetMCB.Q;
|
|
|
|
// Reset error active
|
|
_xErrorActive := FALSE;
|
|
|
|
// Reset warning active
|
|
_xWarningActive := FALSE;
|
|
|
|
// Reset safety interlocks flag
|
|
xSafetyIntlksOk := TRUE;
|
|
|
|
// Copy release manual mode
|
|
_xReleaseManualMode := xReleaseManualMode;
|
|
|
|
// ===============================
|
|
// Valve posolyt tank outlet
|
|
// ===============================
|
|
|
|
// Safety Interlocks
|
|
stHMIInterface.stNS12.stInterlock.asSafetyINTLKName[0] := 'Emergency stop ok';
|
|
_stPosolytValveTankOutletSIntlk.0 := xEmergencyStopOk;
|
|
|
|
// Valve fb
|
|
_fbPosolytValveTankOutlet(
|
|
xReleaseManualMode:= _xReleaseManualMode,
|
|
wProcessINTLK:= _stPosolytValveTankOutletPIntlk,
|
|
wProcessINTLKUsed:= _stPosolytValveTankOutletPIntlkUsed,
|
|
wSafetyINTLK:= _stPosolytValveTankOutletSIntlk,
|
|
wSafetyINTLKUsed:= _stPosolytValveTankOutletSIntlkUsed,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
stValveConfig:= stUnitConfig.stConfigPosolytValve,
|
|
stHMIInterface:= stHMIInterface.stNS12);
|
|
|
|
|
|
// Set error active if fb has error
|
|
IF _fbPosolytValveTankOutlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set safety interlock flag if fb has safety interlocks active
|
|
IF NOT stHMIInterface.stNS12.stInterlock.xSafetyINTLKOk THEN
|
|
xSafetyIntlksOk := FALSE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Valve negolyt tank outlet
|
|
// ===============================
|
|
|
|
// Safety Interlocks
|
|
stHMIInterface.stNS22.stInterlock.asSafetyINTLKName[0] := 'Emergency stop ok';
|
|
_stNegolytValveTankOutletSIntlk.0 := xEmergencyStopOk;
|
|
|
|
// Valve fb
|
|
_fbNegolytValveTankOutlet(
|
|
xReleaseManualMode:= _xReleaseManualMode,
|
|
wProcessINTLK:= _stNegolytValveTankOutletPIntlk,
|
|
wProcessINTLKUsed:= _stNegolytValveTankOutletPIntlkUsed,
|
|
wSafetyINTLK:= _stNegolytValveTankOutletSIntlk,
|
|
wSafetyINTLKUsed:= _stNegolytValveTankOutletSIntlkUsed,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
stValveConfig:= stUnitConfig.stConfigNegolytValve,
|
|
stHMIInterface:= stHMIInterface.stNS22);
|
|
|
|
// Set error active if fb has error
|
|
IF _fbNegolytValveTankOutlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set safety interlock flag if fb has safety interlocks active
|
|
IF NOT stHMIInterface.stNS22.stInterlock.xSafetyINTLKOk THEN
|
|
xSafetyIntlksOk := FALSE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Pump posolyt segment inlet
|
|
// ===============================
|
|
|
|
// Safety Interlocks
|
|
stHMIInterface.stNS11.stInterlock.asSafetyINTLKName[0] := 'Emergency stop ok';
|
|
_stPosolytPumpInletSIntlk.0 := xEmergencyStopOk;
|
|
|
|
// Process interlocks
|
|
stHMIInterface.stNS21.stInterlock.asProcessINTLKName[0] := 'Negolyt Pump Error';
|
|
_stPosolytPumpInletPIntlk.0 := NOT _fbNegolytPumpInlet.xError;
|
|
|
|
|
|
// Pump fb
|
|
_fbPosolytPumpInlet(
|
|
xReleaseManualMode:= _xReleaseManualMode,
|
|
wProcessINTLK:= _stPosolytPumpInletPIntlk,
|
|
wProcessINTLKUsed:= _stPosolytPumpInletPIntlkUsed,
|
|
wSafetyINTLK:= _stPosolytPumpInletSIntlk,
|
|
wSafetyINTLKUsed:= _stPosolytPumpInletSIntlkUsed,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
rSPautomatic:= _rSetpointPosolytPumpInlet,
|
|
xReleaseAnalogInLimitErrors:= xReleaseLimitErrors AND GVL_SCADA.xDummy,
|
|
stMotorAnalogConfig:= stUnitConfig.stConfigPosolytPump,
|
|
stHMIInterface:= stHMIInterface.stNS11,
|
|
xWarning=> );
|
|
|
|
// Set error active if fb has error
|
|
IF _fbPosolytPumpInlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbPosolytPumpInlet.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
// Set safety interlock flag if fb has safety interlocks active
|
|
IF NOT stHMIInterface.stNS11.stInterlock.xSafetyINTLKOk THEN
|
|
xSafetyIntlksOk := FALSE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Pump negolyt segment inlet
|
|
// ===============================
|
|
|
|
// Safety Interlocks
|
|
stHMIInterface.stNS21.stInterlock.asSafetyINTLKName[0] := 'Emergency stop ok';
|
|
_stNegolytPumpInletSIntlk.0 := xEmergencyStopOk;
|
|
|
|
// Process interlocks
|
|
stHMIInterface.stNS11.stInterlock.asProcessINTLKName[0] := 'Posolyt Pump Error';
|
|
_stNegolytPumpInletPIntlk.0 := NOT _fbPosolytPumpInlet.xError;
|
|
|
|
|
|
// Pump fb
|
|
_fbNegolytPumpInlet(
|
|
xReleaseManualMode:= _xReleaseManualMode,
|
|
wProcessINTLK:= _stNegolytPumpInletPIntlk,
|
|
wProcessINTLKUsed:= _stNegolytPumpInletPIntlkUsed,
|
|
wSafetyINTLK:= _stNegolytPumpInletSIntlk,
|
|
wSafetyINTLKUsed:= _stNegolytPumpInletSIntlkUsed,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
rSPautomatic:= _rSetpointNegolytPumpInlet,
|
|
xReleaseAnalogInLimitErrors:= xReleaseLimitErrors AND GVL_SCADA.xDummy,
|
|
stMotorAnalogConfig:= stUnitConfig.stConfigNegolytPump,
|
|
stHMIInterface:= stHMIInterface.stNS21,
|
|
xWarning=> );
|
|
|
|
// Set error active if fb has error
|
|
IF _fbNegolytPumpInlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbNegolytPumpInlet.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
// Set safety interlock flag if fb has safety interlocks active
|
|
IF NOT stHMIInterface.stNS21.stInterlock.xSafetyINTLKOk THEN
|
|
xSafetyIntlksOk := FALSE;
|
|
END_IF
|
|
|
|
_xPumpsReady := stHMIInterface.stNS21.stInterlock.xProcessINTLKOk AND stHMIInterface.stNS21.stInterlock.xSafetyINTLKOk AND stHMIInterface.stNS11.stInterlock.xProcessINTLKOk AND stHMIInterface.stNS11.stInterlock.xSafetyINTLKOk;
|
|
|
|
// ===============================
|
|
// Pressure sensor posolyt segment inlet
|
|
// ===============================
|
|
_fbPressurePosolytSegmentInlet(
|
|
stScalingConfig:= stUnitConfig.stConfigPosolytPressureSegmentInlet,
|
|
stEWConfig:= stUnitConfig.stEWLPosolytPressureSegmentInlet,
|
|
stEWDelayConfig:= stUnitConfig.stEWDPosolytPressureSegmentInlet,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors AND _fbPosolytPumpInlet.IsRunning AND _fbPosolytPumpInlet.xInTarget AND (NOT xStartBalancing) AND (_fbPosolytPumpInlet.rSPautomatic > 40),
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface => stHMIInterface.stP11);
|
|
|
|
// Filter pressure sensor data for HMI
|
|
_rFilteredPressPosolytInlet := _rFilteredPressPosolytInlet * 0.9 + stHMIInterface.stP11.rValue * 0.1;
|
|
stHMIInterface.stP11.rValue := _rFilteredPressPosolytInlet;
|
|
|
|
// Set error active if fb has error
|
|
IF _fbPressurePosolytSegmentInlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbPressurePosolytSegmentInlet.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Pressure sensors negolyt segment inlet
|
|
// ===============================
|
|
_fbPressureNegolytSegmentInlet(
|
|
stScalingConfig:= stUnitConfig.stConfigNegolytPressureSegmentInlet,
|
|
stEWConfig:= stUnitConfig.stEWLNegolytPressureSegmentInlet,
|
|
stEWDelayConfig:= stUnitConfig.stEWDNegolytPressureSegmentInlet,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors AND _fbNegolytPumpInlet.IsRunning AND _fbNegolytPumpInlet.xInTarget AND (NOT xStartBalancing) AND (_fbNegolytPumpInlet.rSPautomatic > 40),
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface => stHMIInterface.stP21);
|
|
|
|
// Filter pressure sensor data for HMI
|
|
_rFilteredPressNegolytInlet := _rFilteredPressNegolytInlet * 0.9 + stHMIInterface.stP21.rValue * 0.1;
|
|
stHMIInterface.stP21.rValue := _rFilteredPressNegolytInlet;
|
|
|
|
// Set error active if fb has error
|
|
IF _fbPressureNegolytSegmentInlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbPressureNegolytSegmentInlet.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Pressure sensors posolyt tank inlet
|
|
// ===============================
|
|
_fbPressurePosolytTankInlet(
|
|
stScalingConfig:= stUnitConfig.stConfigPosolytPressureTankInlet,
|
|
stEWConfig:= stUnitConfig.stEWLPosolytPressureTankInlet,
|
|
stEWDelayConfig:= stUnitConfig.stEWDPosolytPressureTankInlet,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors,
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface => stHMIInterface.stP12);
|
|
|
|
// Filter pressure sensor data for HMI
|
|
_rFilteredPressPosolytTank := _rFilteredPressPosolytTank * 0.9 + stHMIInterface.stP12.rValue * 0.1;
|
|
stHMIInterface.stP12.rValue := _rFilteredPressPosolytTank;
|
|
|
|
// Set error active if fb has error
|
|
IF _fbPressurePosolytTankInlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbPressurePosolytTankInlet.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Pressure sensors negolyt tank inlet
|
|
// ===============================
|
|
_fbPressureNegolytTankInlet(
|
|
stScalingConfig:= stUnitConfig.stConfigNegolytPressureTankInlet,
|
|
stEWConfig:= stUnitConfig.stEWLNegolytPressureTankInlet,
|
|
stEWDelayConfig:= stUnitConfig.stEWDNegolytPressureTankInlet,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors,
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface => stHMIInterface.stP22);
|
|
|
|
// Filter pressure sensor data for HMI
|
|
_rFilteredPressNegolytTank := _rFilteredPressNegolytTank * 0.9 + stHMIInterface.stP22.rValue * 0.1;
|
|
stHMIInterface.stP22.rValue := _rFilteredPressNegolytTank;
|
|
|
|
// Set error active if fb has error
|
|
IF _fbPressureNegolytTankInlet.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbPressureNegolytTankInlet.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Temperature sensor posolyt tank inlet
|
|
// ===============================
|
|
_fbTempSensorPosolyt(
|
|
stScalingConfig:= stUnitConfig.stConfigPosolytTempTankInlet,
|
|
stEWConfig:= GVL_CONFIG.stUnitConfig.stEWLPosolytTempTankInlet,
|
|
stEWDelayConfig:= GVL_CONFIG.stUnitConfig.stEWDPosolytTempTankInlet,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors,
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface=> stHMIInterface.stT11);
|
|
|
|
IF _fbTempSensorPosolyt.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
IF _fbTempSensorPosolyt.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Temperature sensor negolyt tank inlet
|
|
// ===============================
|
|
_fbTempSensorNegolyt(
|
|
stScalingConfig:= stUnitConfig.stConfigNegolytTempTankInlet,
|
|
stEWConfig:= GVL_CONFIG.stUnitConfig.stEWLNegolytTempTankInlet,
|
|
stEWDelayConfig:= GVL_CONFIG.stUnitConfig.stEWDNegolytTempTankInlet,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors,
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface=> stHMIInterface.stT21);
|
|
|
|
IF _fbTempSensorNegolyt.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
IF _fbTempSensorNegolyt.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Voltage segment
|
|
// ===============================
|
|
_fbVoltageSegment(
|
|
stScalingConfig:= GVL_CONFIG.stUnitConfig.stConfigVoltageSegment,
|
|
stEWConfig:= GVL_CONFIG.stUnitConfig.stEWLVoltageSegment,
|
|
stEWDelayConfig:= GVL_CONFIG.stUnitConfig.stEWDVoltageSegment,
|
|
xReleaseErrors:= xReleaseErrors,
|
|
xReleaseLimitErrors:= xReleaseLimitErrors AND _xEnableVoltageLimitChecks,
|
|
xReleaseHardwareErrors:= xReleaseErrors,
|
|
xConfirmAlarms:= xConfirmAlarms,
|
|
stHMIInterface=> stHMIInterface.stE31,
|
|
rScaledValue => rCurrentVoltage);
|
|
|
|
// Set error active if fb has error
|
|
IF _fbVoltageSegment.xError THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
// Set warning if fb has warning
|
|
IF _fbVoltageSegment.xWarning THEN
|
|
_xWarningActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Check for EStop
|
|
// ===============================
|
|
IF (NOT xEmergencyStopOk) THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Write Voltage to HMI
|
|
// ===============================
|
|
stHMIInterface.rVoltage := stHMIInterface.rVoltage * 0.9 + _fbVoltageSegment.rScaledValue * 0.1;
|
|
|
|
|
|
// ===============================
|
|
// Check for pressure difference
|
|
// ===============================
|
|
_xDeltaPSegmentInletToHigh := (ABS(_fbPressurePosolytSegmentInlet.rScaledValue - _fbPressureNegolytSegmentInlet.rScaledValue) > GVL_CONFIG.stUnitConfig.rMaxDeltaPSegmentInlet);
|
|
_xReleaseSignalDeltaPSegment(
|
|
xSignal:= _xDeltaPSegmentInletToHigh,
|
|
xRelease:= _xEnableCheckForDeltaPSegmentInlet,
|
|
timOnDelay:= T#5S,
|
|
timOffDelay:= T#2S,
|
|
xReleaseSignal=> _xErrorDeltaPSegmentInlet);
|
|
|
|
IF _xErrorDeltaPSegmentInlet AND (NOT _fbPressureDiffToBig.bRaised) THEN
|
|
_fbPressureDiffToBig.Raise(0);
|
|
END_IF
|
|
|
|
IF (NOT _xErrorDeltaPSegmentInlet) AND _fbPressureDiffToBig.bRaised THEN
|
|
_fbPressureDiffToBig.Clear(0, FALSE);
|
|
END_IF
|
|
|
|
IF _fbPressureDiffToBig.eConfirmationState = TcEventConfirmationState.WaitForConfirmation THEN
|
|
_fbPressureDiffToBig.Confirm(0);
|
|
END_IF
|
|
|
|
IF _xErrorDeltaPSegmentInlet THEN
|
|
_xErrorActive := TRUE;
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Check if all components are in automatic
|
|
// ===============================
|
|
_xAllComponentsInAutomatic := _fbPosolytValveTankOutlet.IsInAutomaticMode
|
|
AND _fbNegolytValveTankOutlet.IsInAutomaticMode
|
|
AND _fbPosolytPumpInlet.IsInAutomaticMode
|
|
AND _fbNegolytPumpInlet.IsInAutomaticMode;
|
|
|
|
// Raise warning
|
|
IF NOT _fbNotAllAutomaticAlarm.bRaised AND (NOT _xAllComponentsInAutomatic) AND (NOT xAllToManualMode) THEN
|
|
_fbNotAllAutomaticAlarm.Raise(0);
|
|
END_IF
|
|
|
|
// Clear warning and reset
|
|
IF _fbNotAllAutomaticAlarm.bRaised AND _xAllComponentsInAutomatic THEN
|
|
_fbNotAllAutomaticAlarm.Clear(0, TRUE);
|
|
END_IF
|
|
|
|
// Calculate shutdown discharge threshold
|
|
_rShutdownDischargeVoltageThreshold := GVL_CONFIG.rMinimumUnitVoltage + GVL_CONFIG.rDeltaUnitVoltageShutdownDischarge;
|
|
|
|
|
|
// ===============================
|
|
// Run state machine for startup
|
|
// and shutdown
|
|
// NEEDS TO BE CALLED AFTER ALL COMPONENTS BECAUSE OF RESET AND ALARM ACKNOWLEDGEMENT!!!
|
|
// (e.g. restart pumps after estop if segment voltage is still to high)
|
|
// ===============================
|
|
StateMachine();
|
|
|
|
|
|
// ===============================
|
|
// Output error and warning flags
|
|
// ===============================
|
|
xError := _xErrorActive;
|
|
xWarning := _xWarningActive;
|
|
|
|
|
|
// ===============================
|
|
// Handle general error message
|
|
// ===============================
|
|
IF xError AND (NOT _fbUnitError.bRaised) THEN
|
|
_fbUnitError.Raise(0);
|
|
END_IF
|
|
|
|
IF (NOT xError) AND _fbUnitError.bRaised THEN
|
|
_fbUnitError.Clear(0, FALSE);
|
|
END_IF
|
|
|
|
IF _fbUnitError.eConfirmationState = TcEventConfirmationState.WaitForConfirmation AND xConfirmAlarms THEN
|
|
_fbUnitError.Confirm(0);
|
|
END_IF
|
|
|
|
|
|
// ===============================
|
|
// Output all components in auto mode
|
|
// ===============================
|
|
xAllComponentsInAuto := _xAllComponentsInAutomatic;]]></ST>
|
|
</Implementation>
|
|
<Method Name="FB_init" Id="{08f1cd44-6483-4d20-ab45-d1938e8ec885}">
|
|
<Declaration><![CDATA[METHOD FB_init : BOOL
|
|
VAR_INPUT
|
|
bInitRetains : BOOL; // if TRUE, the retain variables are initialized (warm start / cold start)
|
|
bInCopyCode : BOOL; // if TRUE, the instance afterwards gets moved into the copy code (online change)
|
|
|
|
sName : STRING;
|
|
END_VAR
|
|
]]></Declaration>
|
|
<Implementation>
|
|
<ST><![CDATA[_sName := sName;
|
|
|
|
// Create not all components in automatic mode alarm
|
|
_fbNotAllAutomaticAlarm.CreateEx(TC_EVENTS.General.NotAllCompInAutomatic, bWithConfirmation := FALSE, 0);
|
|
_fbNotAllAutomaticAlarm.ipArguments.Clear().AddString(_sName);
|
|
|
|
// Create unit error
|
|
_fbUnitError.CreateEx(stEventEntry := TC_EVENTS.General.UnitError, bWithConfirmation := TRUE, 0);
|
|
_fbUnitError.ipArguments.Clear().AddString(_sName);]]></ST>
|
|
</Implementation>
|
|
</Method>
|
|
<Property Name="Name" Id="{a82783d4-f1f5-481b-bbb0-7ea8279de793}">
|
|
<Declaration><![CDATA[PROPERTY Name : String]]></Declaration>
|
|
<Get Name="Get" Id="{62ca6bce-5aa4-40f1-aa68-f3e5d22ad4a4}">
|
|
<Declaration><![CDATA[VAR
|
|
END_VAR
|
|
]]></Declaration>
|
|
<Implementation>
|
|
<ST><![CDATA[Name := _sName;]]></ST>
|
|
</Implementation>
|
|
</Get>
|
|
<Set Name="Set" Id="{b2e0f6da-5412-45b8-aacd-c140a5beab95}">
|
|
<Declaration><![CDATA[VAR
|
|
END_VAR
|
|
]]></Declaration>
|
|
<Implementation>
|
|
<ST><![CDATA[_sName := Name;
|
|
|
|
// Create alarm message
|
|
_fbNotAllAutomaticAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
|
|
</Implementation>
|
|
</Set>
|
|
</Property>
|
|
<Action Name="StateMachine" Id="{2467f04e-fe89-4b6c-a53d-a49981dd0ce6}">
|
|
<Implementation>
|
|
<ST><![CDATA[// ===============================
|
|
// Run state machine for startup and shutdown
|
|
// ===============================
|
|
CASE _iState OF
|
|
0: // Off
|
|
// Start in enable
|
|
IF xEnable AND (NOT xStartBalancing) AND _xAllComponentsInAutomatic AND (NOT _xErrorActive) THEN
|
|
_xReleaseManualMode := FALSE;
|
|
_timUnitStartupWaitTime := GVL_CONFIG.timUnitStartupTime;
|
|
_iState := 10;
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.STARTING;
|
|
END_IF
|
|
|
|
// Start in balancing mode
|
|
IF (NOT xEnable) AND xStartBalancing AND _xAllComponentsInAutomatic AND (NOT _xErrorActive) THEN
|
|
_xReleaseManualMode := FALSE;
|
|
xBalancingDone := FALSE;
|
|
_timUnitStartupWaitTime := GVL_CONFIG.timUnitBalancingStartupTime;
|
|
_iState := 10;
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
10: // Open all valves
|
|
_fbPosolytValveTankOutlet.ReqAutomaticOpen();
|
|
_fbNegolytValveTankOutlet.ReqAutomaticOpen();
|
|
xOff := FALSE;
|
|
_iState := 15;
|
|
|
|
15: // Wait for all valves to be open
|
|
IF _fbPosolytValveTankOutlet.IsOpen AND _fbNegolytValveTankOutlet.IsOpen THEN
|
|
IF (NOT _fbPosolytValveTankOutlet.xError) AND (NOT _fbNegolytValveTankOutlet.xError) THEN
|
|
_iState := 20;
|
|
END_IF
|
|
END_IF
|
|
|
|
// If enable signal is lost
|
|
IF ((NOT xEnable) AND (NOT xStartBalancing)) THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.SHUTDOWN;
|
|
_iState := 40;
|
|
END_IF
|
|
|
|
// If enable signal is lost, or there is an error, goto shutdown
|
|
IF _xErrorActive THEN
|
|
_xReleaseManualMode := TRUE;
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
IF (NOT xEnable) THEN
|
|
_iState := 51;
|
|
END_IF
|
|
|
|
20: // Start pumps
|
|
_fbPosolytPumpInlet.ReqAutomaticStart();
|
|
_fbNegolytPumpInlet.ReqAutomaticStart();
|
|
_xEnableCheckForDeltaPSegmentInlet := TRUE;
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytOnPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytOnPower;
|
|
|
|
_iState := 25;
|
|
|
|
25: // Wait for all pumps to run
|
|
IF _fbPosolytPumpInlet.xInTarget AND _fbNegolytPumpInlet.xInTarget THEN
|
|
_iState := 30;
|
|
END_IF
|
|
|
|
// If enable signal is lost, goto shutdown
|
|
IF ((NOT xEnable) AND (NOT xStartBalancing)) THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.SHUTDOWN;
|
|
_iState := 40; // 40
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 900;
|
|
END_IF
|
|
|
|
30: // Wait some time
|
|
_tonStartupCheck(In := TRUE, PT := _timUnitStartupWaitTime);
|
|
|
|
// After some time, check if all values are ok
|
|
IF _tonStartupCheck.Q THEN
|
|
_tonStartupCheck(In := FALSE);
|
|
IF xEnable AND (NOT xStartBalancing) THEN
|
|
_iState := 31;
|
|
ELSIF (NOT xEnable) AND xStartBalancing THEN
|
|
xReady := TRUE;
|
|
_iState := 69;
|
|
END_IF
|
|
END_IF
|
|
|
|
// If enable signal is lost, goto shutdown
|
|
IF (NOT xEnable) AND (NOT xStartBalancing) THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.SHUTDOWN;
|
|
_iState := 40;
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 900;
|
|
END_IF
|
|
|
|
31: // Check if voltage limit can be reached
|
|
_tonVoltageCheckTimeput(IN := TRUE);
|
|
|
|
// Check for minimum unit voltage
|
|
IF ((_fbVoltageSegment.rScaledValue >= GVL_CONFIG.rMinimumUnitVoltage) OR xInSafetyCheckMode) AND (NOT _xErrorActive) AND (NOT _xWarningActive) THEN
|
|
_tonVoltageCheckTimeput(IN := FALSE);
|
|
xReady := TRUE;
|
|
|
|
// Only enable Voltage Checks if not in safety check mode
|
|
IF (NOT xInSafetyCheckMode) THEN
|
|
_xEnableVoltageLimitChecks := TRUE;
|
|
END_IF
|
|
|
|
// Continue on normal startup path
|
|
IF xEnable THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.ON;
|
|
_iState := 35;
|
|
END_IF
|
|
|
|
END_IF
|
|
|
|
IF _tonVoltageCheckTimeput.Q OR _xErrorActive THEN
|
|
_tonVoltageCheckTimeput(IN := FALSE);
|
|
xError := TRUE;
|
|
_iState := 900;
|
|
END_IF
|
|
|
|
// If enable signal is lost, goto shutdown
|
|
IF (NOT xEnable) THEN
|
|
_iState := 40;
|
|
END_IF
|
|
|
|
35: // Unit in enabled state
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytOnPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytOnPower;
|
|
|
|
IF (NOT xEnable) THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.SHUTDOWN;
|
|
_iState := 40;
|
|
END_IF
|
|
|
|
// Goto error shutdown if an error occured
|
|
IF _xErrorActive THEN
|
|
_iState := 900;
|
|
END_IF
|
|
|
|
40: // Close all valves
|
|
_fbNegolytValveTankOutlet.ReqAutomaticClose();
|
|
_fbPosolytValveTankOutlet.ReqAutomaticClose();
|
|
xReady := FALSE;
|
|
_iState := 45;
|
|
|
|
45: // Wait for valves to be closed
|
|
IF _fbNegolytValveTankOutlet.IsClosed AND _fbPosolytValveTankOutlet.IsClosed THEN
|
|
xInShutdownDischargeMode := TRUE;
|
|
IF (_fbVoltageSegment.rScaledValue > _rShutdownDischargeVoltageThreshold) THEN
|
|
xShutdownDischargeAllowed := TRUE;
|
|
ELSE
|
|
xShutdownDischargeAllowed := FALSE;
|
|
END_IF
|
|
_iState := 50;
|
|
END_IF
|
|
|
|
// When there is an error trying to close the valves,
|
|
// dont try to discharge the segment
|
|
IF _fbNegolytValveTankOutlet.xError OR _fbPosolytValveTankOutlet.xError THEN
|
|
_xEnableVoltageLimitChecks := FALSE;
|
|
_iState := 60;
|
|
END_IF
|
|
|
|
// Check for restart condition
|
|
IF xEnable AND (NOT _xErrorActive) THEN
|
|
_iState := 0;
|
|
END_IF
|
|
|
|
50: // Wait for unit voltage to drop below a certain threshold
|
|
IF (_fbVoltageSegment.rScaledValue > _rShutdownDischargeVoltageThreshold) AND xInverterEnabled THEN
|
|
xShutdownDischargeAllowed := TRUE;
|
|
ELSE
|
|
xShutdownDischargeAllowed := FALSE;
|
|
_xEnableVoltageLimitChecks := FALSE;
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytDisChrgPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytDisChrgPower;
|
|
_xEnableCheckForDeltaPSegmentInlet := FALSE;
|
|
_iState := 51;
|
|
END_IF
|
|
|
|
// Check for restart condition
|
|
IF (xEnable OR xStartBalancing) AND (NOT _xErrorActive) THEN
|
|
xShutdownDischargeAllowed := FALSE;
|
|
xInShutdownDischargeMode := FALSE;
|
|
_iState := 0;
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
51: // Discharge without inverter
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytDisChrgPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytDisChrgPower;
|
|
|
|
IF (_fbVoltageSegment.rScaledValue <= GVL_CONFIG.rPumpshutoffThreshold) THEN
|
|
xShutdownDischargeAllowed := FALSE;
|
|
xInShutdownDischargeMode := FALSE;
|
|
_iState := 60;
|
|
END_IF
|
|
|
|
// Check for restart condition
|
|
IF xEnable AND (NOT _xErrorActive) THEN
|
|
xShutdownDischargeAllowed := FALSE;
|
|
xInShutdownDischargeMode := FALSE;
|
|
_iState := 0;
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
60: // Disable pumps
|
|
_fbPosolytPumpInlet.ReqAutomaticStop();
|
|
_fbNegolytPumpInlet.ReqAutomaticStop();
|
|
_iState := 65;
|
|
|
|
65: // Wait for pumps to be stopped
|
|
IF _fbPosolytPumpInlet.IsStopped AND _fbNegolytPumpInlet.IsStopped THEN
|
|
xOff := TRUE;
|
|
_xReleaseManualMode := TRUE;
|
|
IF NOT _xErrorActive THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.OFF;
|
|
_iState := 0;
|
|
END_IF
|
|
END_IF
|
|
|
|
// Check for restart condition
|
|
IF xEnable AND (NOT _xErrorActive) THEN
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.OFF;
|
|
_iState := 0;
|
|
END_IF
|
|
|
|
// Check for error
|
|
IF _xErrorActive THEN
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
69: // Check for minimum voltage
|
|
IF (_fbVoltageSegment.rScaledValue <= GVL_CONFIG.rMinimumUnitVoltage) THEN
|
|
_iState := 900;
|
|
ELSE
|
|
_rBalancingTargetVoltage := rBalancingTargetVoltage;
|
|
_istate := 70;
|
|
END_IF
|
|
|
|
70: // Wait for segment voltage to be in the range of the target voltage
|
|
IF (_fbVoltageSegment.rScaledValue <= _rBalancingTargetVoltage) THEN
|
|
xBalancingDone := TRUE;
|
|
_iState := 71;
|
|
END_IF
|
|
|
|
// If enable signal is lost, goto shutdown
|
|
IF (NOT xStartBalancing) THEN
|
|
_iState := 40;
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 900;
|
|
END_IF
|
|
|
|
71: // Close valves
|
|
_fbNegolytValveTankOutlet.ReqAutomaticClose();
|
|
_fbPosolytValveTankOutlet.ReqAutomaticClose();
|
|
xReady := FALSE;
|
|
_iState := 72;
|
|
|
|
72: // Wait for all valves to be closed
|
|
IF _fbNegolytValveTankOutlet.IsClosed AND _fbPosolytValveTankOutlet.IsClosed THEN
|
|
xInShutdownDischargeMode := TRUE;
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytDisChrgPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytDisChrgPower;
|
|
_iState := 73;
|
|
END_IF
|
|
|
|
73: // Wait for start balancing signal to be off to prevent automatic restart
|
|
IF (NOT xStartBalancing) THEN
|
|
_iState := 50;
|
|
END_IF
|
|
|
|
700: // Debug step
|
|
IF (NOT xStartBalancing) THEN
|
|
_iState := 40;
|
|
END_IF
|
|
|
|
900: // Soft error shutdown
|
|
_fbNegolytValveTankOutlet.ReqAutomaticClose();
|
|
_fbPosolytValveTankOutlet.ReqAutomaticClose();
|
|
|
|
_xEnableCheckForDeltaPSegmentInlet := FALSE;
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytDisChrgPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytDisChrgPower;
|
|
|
|
_fbNegolytPumpInlet.ReqAutomaticStart();
|
|
_fbPosolytPumpInlet.ReqAutomaticStart();
|
|
|
|
_xEnableVoltageLimitChecks := FALSE;
|
|
xShutdownDischargeAllowed := FALSE;
|
|
xInShutdownDischargeMode := FALSE;
|
|
xReady := FALSE;
|
|
|
|
_iState := 910;
|
|
|
|
910: // Wait for discharged or restart
|
|
IF (_fbVoltageSegment.rScaledValue <= GVL_CONFIG.rPumpshutoffThreshold) THEN
|
|
xShutdownDischargeAllowed := FALSE;
|
|
xInShutdownDischargeMode := FALSE;
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
// Check for restart condition
|
|
IF (NOT xEnable) AND xError THEN
|
|
xError := FALSE;
|
|
END_IF
|
|
|
|
IF (NOT xError) AND (xEnable OR xStartBalancing) THEN
|
|
_iState := 0;
|
|
END_IF
|
|
|
|
IF _xErrorActive THEN
|
|
_iState := 1000;
|
|
END_IF
|
|
|
|
1000: // Error shutdown
|
|
stHMIInterface.eStatus := E_COMPONENT_STATUS.ERROR;
|
|
_fbNegolytValveTankOutlet.ReqAutomaticClose();
|
|
_fbPosolytValveTankOutlet.ReqAutomaticClose();
|
|
_fbPosolytPumpInlet.ReqAutomaticStop();
|
|
_fbNegolytPumpInlet.ReqAutomaticStop();
|
|
_xEnableVoltageLimitChecks := FALSE;
|
|
xShutdownDischargeAllowed := FALSE;
|
|
xInShutdownDischargeMode := FALSE;
|
|
xReady := FALSE;
|
|
xOff := TRUE;
|
|
xError := TRUE;
|
|
_iState := 1001;
|
|
|
|
1001: // Alarm active
|
|
// Only allow reset when enable is deactivated to avoid an
|
|
// automatic restart of the unit
|
|
IF (NOT _xErrorActive) AND (NOT xEnable) AND (NOT xStartBalancing) AND _xPumpsReady AND xConfirmAlarms THEN
|
|
xError := FALSE;
|
|
IF (_fbVoltageSegment.rScaledValue >= GVL_CONFIG.rPumpshutoffThreshold) THEN
|
|
_iState := 1002;
|
|
ELSE
|
|
_iState := 0;
|
|
END_IF
|
|
END_IF
|
|
|
|
1002:
|
|
_rSetpointNegolytPumpInlet := GVL_CONFIG.rPumpNegolytDisChrgPower;
|
|
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytDisChrgPower;
|
|
|
|
_fbNegolytPumpInlet.ReqAutomaticStart();
|
|
_fbPosolytPumpInlet.ReqAutomaticStart();
|
|
_iState := 51;
|
|
END_CASE]]></ST>
|
|
</Implementation>
|
|
</Action>
|
|
</POU>
|
|
</TcPlcObject> |