Uniper error tests:
===================
// Error high posolyt
xErrorHighPressurePosolytSegmentInlet -> OK
xErrorHighPressurePosolytTankInlet -> OK
xErrorHighTempPosolyt -> OK
// Error high negolyt
xErrorHighPressureNegolytSegmentInlet -> OK
xErrorHighPressureNegolytTankInlet -> OK
xErrorHighTempNegolyt -> OK
// Error low posolyt
xErrorLowPressurePosolytSegmentInlet -> OK
xErrorLowPressurePosolytTankInlet -> OK
xErrorLowTempPosolyt -> OK
// Error low negolyt
xErrorLowPressureNegolytSegmentInlet -> OK
xErrorLowPressureNegolytTankInlet -> OK
xErrorLowTempNegolyt -> OK
// Error valve posolyt
xErrorOpenValvePosolyt -> Keine Fehlermeldung
xErrorCloseValvePosolyt -> OK
// Error valve negolyt
xErrorOpenValveNegolyt -> Keine Fehlermeldung
xErrorCloseValveNegolyt -> OK
// Error voltage segment
xErrorHighVoltageSegment -> OK (Zum testen den Balance check im Modul und string abschalten)
xErrorLowVoltageSegment -> OK (Zum testen den Balance check im Modul und string abschalten)
// MCB ok pump posolyt
xMCBOkPumpPosolyt -> OK
// Repair switch ok pump posolyt
xRepairSwitchOkPumpPosolyt -> Kein Reparaturschalter vorhanden
// MCB ok pump negolyt
xMCBOkPumpNegolyt -> OK
// Repair switch ok pump negolyt
xRepairSwitchOkPumpNegolyt -> Kein Reparaturschalter vorhanden