added sync units for cabinet temperature, changes in modbus interface to EMS (1.0.4 and 1.0.5), added error counter to modbus communication, lot of changes to kaco (faults, consecutive errors, bms error messages), isolation error ledge, allowed startbalancing when on shutdown, tower light integration
300 lines
9.9 KiB
XML
300 lines
9.9 KiB
XML
<?xml version="1.0" encoding="utf-8"?>
|
|
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.12">
|
|
<GVL Name="GVL_CONFIG" Id="{0773bf51-0237-454d-a970-cfd896054edb}">
|
|
<Declaration><![CDATA[{attribute 'qualified_only'}
|
|
VAR_GLOBAL CONSTANT
|
|
// ===========================
|
|
// Number of active strings
|
|
// ===========================
|
|
uiNumberOfStrings : UINT := 2;
|
|
uiNumberOfUnits : UINT := uiNumberOfStrings * 12;
|
|
END_VAR
|
|
VAR_GLOBAL PERSISTENT
|
|
axStringEnabled : ARRAY [0..uiNumberOfStrings-1] OF BOOL;
|
|
|
|
// ===========================
|
|
// Unit hardware config
|
|
// ===========================
|
|
stUnitConfig : ST_UNIT_CONFIG :=
|
|
(
|
|
// Pump poslyt segment inlet
|
|
stConfigPosolytPump :=
|
|
(
|
|
rTargetMin := 0.0,
|
|
rTargetMax := 100.0,
|
|
timRampUpTime := T#10S,
|
|
timRampDownTime := T#10S,
|
|
stAnalogInputConfig := (iAIMax := 108, iAIMin := 0, rPVMax := 100, rPVMin := 0, sUnit := '%'),
|
|
stAnalogOutputConfig := (iAIMax := 29490, iAIMin := 0, rPVMax := 100, rPVMin := 4.807),
|
|
xHasAnalogFeedback := TRUE,
|
|
xHasMCBFeedback := TRUE,
|
|
xHasRepairSwitchFeedback := FALSE
|
|
),
|
|
|
|
// Pump negolyt segment inlet
|
|
stConfigNegolytPump :=
|
|
(
|
|
rTargetMin := 0.0,
|
|
rTargetMax := 100.0,
|
|
timRampUpTime := T#5S,
|
|
timRampDownTime := T#5S,
|
|
stAnalogInputConfig := (iAIMax := 108, iAIMin := 0, rPVMax := 100, rPVMin := 0, sUnit := '%'),
|
|
stAnalogOutputConfig := (iAIMax := 29490, iAIMin := 0, rPVMax := 100, rPVMin := 4.807),
|
|
xHasAnalogFeedback := TRUE,
|
|
xHasMCBFeedback := TRUE,
|
|
xHasRepairSwitchFeedback := FALSE
|
|
),
|
|
|
|
// Valve posolyt tank outlet
|
|
stConfigPosolytValve := (timTimeoutOpen := T#10S, timTimeoutClose := T#10S, xHasOpenFeedback := TRUE, xHasClosedFeedback := TRUE),
|
|
|
|
// Valve negolyt tank outlet
|
|
stConfigNegolytValve := (timTimeoutOpen := T#10S, timTimeoutClose := T#10S, xHasOpenFeedback := TRUE, xHasClosedFeedback := TRUE),
|
|
|
|
// Pressure posolyt segment inlet
|
|
stConfigPosolytPressureSegmentInlet := (iAIMax := 32767, iAIMin := 0, rPVMax := 2000, rPVMin := 0, sUnit := 'mbar'),
|
|
stEWLPosolytPressureSegmentInlet := (rErrorMin := 200, rWarningMin := 250, rWarningMax := 550, rErrorMax := 600),
|
|
stEWDPosolytPressureSegmentInlet :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
// Pressure negolyt segment inlet
|
|
stConfigNegolytPressureSegmentInlet := (iAIMax := 32767, iAIMin := 0, rPVMax := 2000, rPVMin := 0, sUnit := 'mbar'),
|
|
stEWLNegolytPressureSegmentInlet := (rErrorMin := 200, rWarningMin := 250, rWarningMax := 550, rErrorMax := 600),
|
|
stEWDNegolytPressureSegmentInlet :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
// Pressure posolyt tank inlet
|
|
stConfigPosolytPressureTankInlet := (iAIMax := 32767, iAIMin := 0, rPVMax := 2000, rPVMin := 0, sUnit := 'mbar'),
|
|
stEWLPosolytPressureTankInlet := (rErrorMin := -20, rWarningMin := -10, rWarningMax := 50, rErrorMax := 75),
|
|
stEWDPosolytPressureTankInlet :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
// Pressure negolyt tank inlet
|
|
stConfigNegolytPressureTankInlet := (iAIMax := 32767, iAIMin := 0, rPVMax := 2000, rPVMin := 0, sUnit := 'mbar'),
|
|
stEWLNegolytPressureTankInlet := (rErrorMin := -20, rWarningMin := -10, rWarningMax := 50, rErrorMax := 75),
|
|
stEWDNegolytPressureTankInlet :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
// Temperature sensor posolyt tank inlet
|
|
stConfigPosolytTempTankInlet := (iAIMax := 32767, iAIMin := -32768, rPVMax := 3276.7, rPVMin := -3276.8, sUnit := '°C'),
|
|
stEWLPosolytTempTankInlet := (rErrorMin := 10, rWarningMin := 15, rWarningMax := 42, rErrorMax := 45),
|
|
stEWDPosolytTempTankInlet :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
// Temperature sensor negolyt tank inlet
|
|
stConfigNegolytTempTankInlet := (iAIMax := 32767, iAIMin := -32768, rPVMax := 3276.7, rPVMin := -3276.8, sUnit := '°C'),
|
|
stEWLNegolytTempTankInlet := (rErrorMin := 15, rWarningMin := 15, rWarningMax := 42, rErrorMax := 45),
|
|
stEWDNegolytTempTankInlet :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
// Voltage sensor segment
|
|
// EL3214-0090 CoE Verzeichnis
|
|
// Index 0x80n0:02 "Presentation" = Signed(0) -> Resolution 1/10°C
|
|
// Index 0x80n0:19 "RTD Element" = PT100(0)
|
|
stConfigVoltageSegment := (iAIMax := 32767, iAIMin := 0, rPVMax := 150, rPVMin := 0, sUnit := 'V'),
|
|
stEWLVoltageSegment := (rErrorMin := 50, rWarningMin := 54, rWarningMax := 79, rErrorMax := 80),
|
|
stEWDVoltageSegment :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
),
|
|
|
|
rMaxDeltaPSegmentInlet := 50.0
|
|
);
|
|
|
|
// ===========================
|
|
// SCS Current measurement settings
|
|
// ===========================
|
|
stConfigSCSCurrent : ST_ANALOG_IO_CONFIG := (iAIMax := 32767, iAIMin := 0, rPVMax := 200, rPVMin := 0, sUnit := 'A');
|
|
stEWLSCSCurrent : ST_ANALOG_EW_LEVELS;
|
|
stEWDSCSCurrent : ST_ANALOG_EW_DELAYS;
|
|
|
|
// ===========================
|
|
// Control cabinet temperature sensor config
|
|
// ===========================
|
|
// Temperature sensor control cabinets
|
|
stConfigCabinetTemp : ST_ANALOG_IO_CONFIG := (iAIMax := 32767, iAIMin := -32768, rPVMax := 3276.7, rPVMin := -3276.8, sUnit := '°C');
|
|
stEWLCabinetTemp : ST_ANALOG_EW_LEVELS := (rErrorMin := -20, rWarningMin := -15, rWarningMax := 40, rErrorMax := 80);
|
|
stEWDCabinetTemp : ST_ANALOG_EW_DELAYS :=
|
|
(
|
|
timHardwareSignalLevelOn := T#0S,
|
|
timHardwareSignalLevelOff := T#5S,
|
|
timErrorLowOn := T#1S,
|
|
timErrorLowOff := T#5S,
|
|
timWarningLowOn := T#1S,
|
|
timWarningLowOff := T#5S,
|
|
timWarningHighOn := T#1S,
|
|
timWarningHighOff := T#5S,
|
|
timErrorHighOn := T#1S,
|
|
timErrorHighOff := T#5S
|
|
);
|
|
|
|
|
|
// ===========================
|
|
// General settings
|
|
// ===========================
|
|
|
|
// Pump posolyt on power in %
|
|
rPumpPosolytOnPower : REAL := 70.0;
|
|
|
|
// Pump negolyt on power in %
|
|
rPumpNegolytOnPower : REAL := 70.0;
|
|
|
|
// Pump posolyt discharge segment without inverter power in %
|
|
rPumpPosolytDisChrgPower : REAL := 50.0;
|
|
|
|
// Pump posolyt discharge segment without inverter power in %
|
|
rPumpNegolytDisChrgPower : REAL := 50.0;
|
|
|
|
// Unit voltage pumps shutoff threshold (Volt)
|
|
rPumpshutoffThreshold : REAL := 15.0;
|
|
|
|
// Minimum unit voltage required for inverter startup (Volt)
|
|
rMinimumUnitVoltage : REAL := 55.0;
|
|
|
|
// Maximum unit voltage for fully charged (Volt)
|
|
rMaximumUnitVoltage : REAL := 78.5;
|
|
|
|
// Delta value to minimum unit voltage for shutdown discharge (Volt)
|
|
rDeltaUnitVoltageShutdownDischarge : REAL := 5.0;
|
|
|
|
// Maximum absolute voltage difference
|
|
// between units in the same module
|
|
rMaxAbsDiffVoltageUnitsOnModule : REAL := 10.0;
|
|
|
|
// Maximum absolute voltage difference
|
|
// between Modules (Volt)
|
|
rMaxAbsDiffVoltageModulesInString : REAL := 20.0;
|
|
|
|
// Minimum absolute power command to enable battery (Watt)
|
|
diMinimumAbsPowerForEnable : DINT := 100;
|
|
|
|
// Maximum allowed charging power (Watt) per String
|
|
// 24.000 W -> 2.000 W per Unit
|
|
diMaxStringChargingPower : DINT := -48_000;
|
|
|
|
// Maximum allowed discharging power (Watt) per String
|
|
// 24.000 W -> 2.000 W per Unit
|
|
diMaxStringDischargePower : DINT := 48_000;
|
|
|
|
// Inverter ip address for string 1
|
|
sInverterIpString1 : STRING := '192.168.42.10';
|
|
|
|
// Inverter ip address for string 2
|
|
sInverterIpString2 : STRING := '192.168.42.20';
|
|
|
|
// Absolute shutdown discharge power (Watt)
|
|
// 12.000 W -> 1.000 W per unit
|
|
rAbsShutdownDischargePower : REAL := 6_500;
|
|
|
|
// Allow inverter fast shutdown discharge
|
|
xShutdownDischargeWithInverter : BOOL := FALSE;
|
|
|
|
// String fully charged voltage (Volt)
|
|
// 960 V -> 80 V per Unit
|
|
rStringFullyChargedVoltage : REAL := 960.0;
|
|
|
|
// String empty voltage (Volt) (617V is needed for the inverter to start up -> 55.0V per Segment)
|
|
rStringEmptyVoltage : REAL := 660.0;
|
|
|
|
// Unit wait startup time (was 1 minute, reduced because of Doppelhöcker-Test)
|
|
timUnitStartupTime : TIME := T#15S;
|
|
|
|
// Unit balancing wait startup time
|
|
timUnitBalancingStartupTime : TIME := T#3M;
|
|
|
|
// All modules in string not ready timeout
|
|
timStringReadyTimeout : TIME := T#3M;
|
|
|
|
// Timeout for isolation error
|
|
timIsoErrorTimeout : TIME := T#20S;
|
|
|
|
// Balancing factor
|
|
rBalancingFactor : REAL := 20.0;
|
|
|
|
// Timeout heartbeat from EMS
|
|
timEMSHeartbeatTimeout : TIME := t#5s;
|
|
|
|
// Dummy to deactivate functions
|
|
{attribute 'analysis' := '-33'}
|
|
xDummy : BOOL := FALSE;
|
|
|
|
udiMaxConsecutiveInvError : UDINT := 10;
|
|
|
|
END_VAR]]></Declaration>
|
|