<Declaration><![CDATA[FUNCTION_BLOCK FB_Hotplate EXTENDS FB_PackMLGeneric
|
||||
VAR_INPUT
|
||||
xEnable : BOOL;
|
||||
rTargetTemp : REAL;
|
||||
|
||||
xReleaseAlarms : BOOL;
|
||||
xConfirmAlarms : BOOL;
|
||||
END_VAR
|
||||
VAR_OUTPUT
|
||||
uiNextFreeSlot : UINT;
|
||||
uiNextReadySlot : UINT;
|
||||
END_VAR
|
||||
VAR_IN_OUT
|
||||
stHMIInterface : ST_HMI_Hotplate;
|
||||
END_VAR
|
||||
VAR
|
||||
xEnableHotplate AT %Q* : BOOL;
|
||||
|
||||
// _axSlotFree : ARRAY [0..(GVL_HeatCoolConfig.HEAT_COOL_PLATES_NUM_SLOTS - 1)] OF BOOL;
|
||||
// _atonSlotTimer : ARRAY[0..(GVL_HeatCoolConfig.HEAT_COOL_PLATES_NUM_SLOTS - 1)] OF TON;
|
||||
|
||||
// Temp sensor
|
||||
_fbTempSensor : FB_AnalogInput('Temp sensor');
|
||||
_stTempSensorConfig : ST_ANALOG_IO_CONFIG := (sUnit := '°C', rPVMin := -200, rPVMax := 850, iAIMin := -2000, iAIMax := 8500);
|
||||
_stTempSEnsorEWConfig : ST_ANALOG_EW_CONFIG := (
|
||||
stLevels := (
|
||||
rErrorMin := -2000,
|
||||
rErrorMax := 8500,
|
||||
rWarningMin := -1000,
|
||||
rWarningMax := 7500),
|
||||
stDelays := (
|
||||
timErrorHighOn := T#1S,
|
||||
timErrorLowOn := T#1S,
|
||||
timWarningHighOn := T#1S,
|
||||
timWarningLowOn := T#1S,
|
||||
timHardwareSignalLevelOff := T#1S));
|
||||
|
||||
_fbPITempControl : FB_PI;
|
||||
_fbLimit : FB_Limit;
|
||||
_fbPWMOut : FB_PWM;
|
||||
|
||||
_xEnable : BOOL;
|
||||
|
||||
_xFirstCycle : BOOL := TRUE;
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[IF _xFirstCycle THEN
|
||||
_xFirstCycle := FALSE;
|
||||
|
||||
stHMIInterface.stSetpoint.rMin := 0;
|
||||
stHMIInterface.stSetpoint.rMax := 140.0;
|
||||
stHMIInterface.stSetpoint.sUnit := '°C';
|
||||
stHMIInterface.stSetpoint.sName := 'Temp. Hotplate';
|
||||
END_IF
|
||||
|
||||
A_HandleHMIInput();
|
||||
|
||||
// Call sensor fbs
|
||||
_fbTempSensor(
|
||||
stAnalogIOConfig:= _stTempSensorConfig,
|
||||
stAnalogEWConfig:= _stTempSEnsorEWConfig,
|
||||
xReleaseErrors:= xReleaseAlarms,
|
||||
xReleaseLimitErrors:= FALSE,
|
||||
xReleaseHardwareErrors:= TRUE,
|
||||
xConfirmAlarms:= xConfirmAlarms,
|
||||
stHMIInterface=> stHMIInterface.stPV);
|
||||
|
||||
// For now get setpoint from HMI interface
|
||||
_fbPITempControl(
|
||||
rSP:= stHMIInterface.stSetpoint.rValue,
|
||||
rPV:= _fbTempSensor.rScaledValue,
|
||||
rKp:= 6,
|
||||
rTn:= 0,
|
||||
xEnable:= _xEnable,
|
||||
rMV=> _fbLimit.rIn);
|
||||
|
||||
_fbLimit(
|
||||
rMin:= 0,
|
||||
rMax:= 100.0,
|
||||
rOut=> _fbPWMOut.rPWM,
|
||||
xClampedUpper=> _fbPITempControl.xSaturatedUpper,
|
||||
xClampedLower=> _fbPITempControl.xSaturatedLower);
|
||||
|
||||
_fbPWMOut(
|
||||
timPeriod:= T#100MS,
|
||||
xOutput=> xEnableHotplate);
|
||||
|
||||
SUPER^(stPackMLHMIInterface := stHMIInterface.stStationCmds);
|
||||
]]></ST>
|
||||
</Implementation>
|
||||
<Action Name="A_HandleHMIInput" Id="{d22cec08-4a88-4001-b04b-e7a9775ff9a8}">
|
||||
<Implementation>
|
||||
<ST><![CDATA[// Clamp HMI Setpoint
|
||||
IF stHMIInterface.stSetpoint.rValue > 140.0 THEN
|
||||
stHMIInterface.stSetpoint.rValue := 140;
|
||||
END_IF
|
||||
|
||||
IF stHMIInterface.stSetpoint.rValue < 0.0 THEN
|
||||
stHMIInterface.stSetpoint.rValue := 0.0;
|
||||
END_IF]]></ST>
|
||||
</Implementation>
|
||||
</Action>
|
||||
<Method Name="FB_Init" Id="{b45cedd9-9c6c-4658-b56c-da5577886b8f}">
|
||||
<Declaration><![CDATA[//FB_Init is always available implicitly and it is used primarily for initialization.
|
||||
//The return value is not evaluated. For a specific influence, you can also declare the
|
||||
//methods explicitly and provide additional code there with the standard initialization
|
||||
//code. You can evaluate the return value.
|
||||
METHOD FB_Init: BOOL
|
||||
VAR_INPUT
|
||||
bInitRetains: BOOL; // TRUE: the retain variables are initialized (reset warm / reset cold)
|
||||
bInCopyCode: BOOL; // TRUE: the instance will be copied to the copy code afterward (online change)
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[]]></ST>
|
||||
</Implementation>
|
||||
</Method>
|
||||
<Method Name="M_AddItem" Id="{9707459a-6558-487c-b730-c9dc92d598ed}">
|
||||
<Declaration><![CDATA[METHOD M_AddItem
|
||||
VAR_INPUT
|
||||
END_VAR
|
||||
]]></Declaration>
|
||||
<Implementation>
|
||||
<ST><![CDATA[]]></ST>
|
||||
</Implementation>
|
||||
</Method>
|
||||
</POU>
|
||||
</TcPlcObject>
|
||||