<?xml version="1.0" encoding="utf-8"?>
<TcPlcObject Version="1.1.0.1">
<POU Name="FB_PWM" Id="{39ea0d97-8eb7-44fa-b55f-8461b6c6c8ae}" SpecialFunc="None">
<Declaration><![CDATA[FUNCTION_BLOCK FB_PWM
VAR_INPUT
rPWM : REAL;
timPeriod : TIME;
END_VAR
VAR_OUTPUT
xOutput : BOOL;
END_VAR
VAR
_tonTimer : TON;
END_VAR
]]></Declaration>
<Implementation>
<ST><![CDATA[// Check for possible division by zero
IF TIME_TO_REAL(timPeriod) = 0 THEN
xOutput := FALSE;
RETURN;
END_IF
_tonTimer(IN := TRUE, PT := timPeriod);
IF _tonTimer.Q THEN
_tonTimer(IN := FALSE);
END_IF
IF rPWM = 0.0 THEN
xOutput := FALSE;
ELSIF rPWM >= 100.0 THEN
xOutput := TRUE;
ELSE
IF (1.0 - (TIME_TO_REAL(_tonTimer.ET) / TIME_TO_REAL(timPeriod))) <= (rPWM * 0.01) THEN
xOutput := TRUE;
ELSE
xOutput := FALSE;
END_IF
END_IF]]></ST>
</Implementation>
</POU>
</TcPlcObject>