- Added new module status

- Added error messages for EtherCAT connection lost
This commit is contained in:
Matthias Heisig
2024-09-05 18:32:49 +02:00
parent 5e94ba4868
commit 3d041c50c4
8 changed files with 607 additions and 318 deletions

View File

@@ -1,5 +1,5 @@
<?xml version="1.0" encoding="utf-8"?>
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4024.12">
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.8">
<DUT Name="E_COMPONENT_STATUS" Id="{cff71c34-33b2-4724-933e-1a2c018acdb7}">
<Declaration><![CDATA[{attribute 'qualified_only'}
{attribute 'strict'}
@@ -10,7 +10,9 @@ TYPE E_COMPONENT_STATUS :
ON := 1,
CHARGING := 2,
DISCHARGING := 3,
ERROR := 4
ERROR := 4,
SHUTDOWN := 5,
STARTING := 6
);
END_TYPE
]]></Declaration>

File diff suppressed because one or more lines are too long

View File

@@ -1,5 +1,5 @@
<?xml version="1.0" encoding="utf-8"?>
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.7">
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.8">
<POU Name="FB_Module" Id="{87be924f-018d-4c09-997b-f0c0054414cc}" SpecialFunc="None">
<Declaration><![CDATA[FUNCTION_BLOCK FB_Module
VAR_INPUT
@@ -56,6 +56,8 @@ VAR_INPUT
// Leakage tank
xLeakageTank AT %I* : BOOL;
xECState AT %I* : UINT;
END_VAR
VAR_OUTPUT
// Module voltage
@@ -103,6 +105,9 @@ VAR
// Units out of balance alarm
_fbUnitsOutOfBalanceAlarm : FB_TcAlarm;
// Connection lost alarm
_fbConnLostAlarm : FB_TcAlarm;
// Enable balance check
_xEnableBalanceCheck : BOOL;
@@ -115,6 +120,8 @@ VAR
_fbBalanceNotOkSignal : FB_ReleaseSignal;
_xECModuleInOP : BOOL;
xDebug1 : BOOL;
xDebug2 : BOOL;
xDebug3 : BOOL;
@@ -132,6 +139,22 @@ xAllUnitsInAutomatic := TRUE;
// Reset safety interlocks flag
xSafetyIntlksOk := TRUE;
// ===============================
// Handle module connection lost error
// ===============================
_xECModuleInOP := (xECState AND 16#000F) = 8;
IF (NOT _xECModuleInOP) AND (NOT _fbConnLostAlarm.bRaised) AND xReleaseErrors THEN
_fbConnLostAlarm.Raise(0);
END_IF
IF (_xECModuleInOP) AND _fbConnLostAlarm.bRaised THEN
_fbConnLostAlarm.Clear(0, FALSE);
END_IF
IF _fbConnLostAlarm.eConfirmationState = TcEventConfirmationState.WaitForConfirmation AND xConfirmAlarms THEN
_fbConnLostAlarm.Confirm(0);
END_IF
// ===============================
// Unit 1
@@ -407,17 +430,26 @@ rHighestSegmentVoltage := MAX(_fbUnit1.rCurrentVoltage, _fbUnit2.rCurrentVoltage
// ===============================
// Module status sum
// ===============================
IF xOff THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.OFF;
IF xReady AND (NOT xError) THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.ON;
END_IF
IF xReady THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.ON;
IF (_fbUnit1.eUnitState = E_COMPONENT_STATUS.STARTING OR _fbUnit1.eUnitState = E_COMPONENT_STATUS.STARTING OR _fbUnit1.eUnitState = E_COMPONENT_STATUS.STARTING OR _fbUnit1.eUnitState = E_COMPONENT_STATUS.STARTING) AND (NOT xError) THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.STARTING;
END_IF
IF (_fbUnit1.eUnitState = E_COMPONENT_STATUS.SHUTDOWN OR _fbUnit1.eUnitState = E_COMPONENT_STATUS.SHUTDOWN OR _fbUnit1.eUnitState = E_COMPONENT_STATUS.SHUTDOWN OR _fbUnit1.eUnitState = E_COMPONENT_STATUS.SHUTDOWN) AND (NOT xError) THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.SHUTDOWN;
END_IF
IF (_fbUnit1.eUnitState = E_COMPONENT_STATUS.OFF AND _fbUnit1.eUnitState = E_COMPONENT_STATUS.OFF AND _fbUnit1.eUnitState = E_COMPONENT_STATUS.OFF AND _fbUnit1.eUnitState = E_COMPONENT_STATUS.OFF) AND (NOT xError) THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.OFF;
END_IF
IF xError THEN
stHMIInterface.eStatus := E_COMPONENT_STATUS.ERROR;
END_IF]]></ST>
END_IF
]]></ST>
</Implementation>
<Method Name="FB_init" Id="{369c1d27-76e4-45f8-9dbe-03524d3389df}">
<Declaration><![CDATA[METHOD FB_init : BOOL
@@ -443,6 +475,11 @@ _fbUnitsOutOfBalanceAlarm.CreateEx(stEventEntry := TC_EVENTS.BMSEvents.ModuleImb
// Create alarm message
_fbUnitsOutOfBalanceAlarm.ipArguments.Clear().AddString(_sName);
// Create connection lost alarm
_fbConnLostAlarm.CreateEx(stEventEntry := TC_EVENTS.General.CommError, bWithConfirmation := TRUE, 0);
_fbConnLostAlarm.ipArguments.Clear().AddString(_sName);
// Create leakage alarm messages
]]></ST>
</Implementation>
@@ -471,9 +508,59 @@ _fbUnit3.Name := CONCAT(_sName, ' - Unit 3');
_fbUnit4.Name := CONCAT(_sName, ' - Unit 4');
// Create alarm message
_fbUnitsOutOfBalanceAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
_fbUnitsOutOfBalanceAlarm.ipArguments.Clear().AddString(_sName);
// Create connection lost alarm
_fbConnLostAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
</Implementation>
</Set>
</Property>
<LineIds Name="FB_Module">
<LineId Id="3" Count="8" />
<LineId Id="338" Count="0" />
<LineId Id="340" Count="1" />
<LineId Id="339" Count="0" />
<LineId Id="352" Count="0" />
<LineId Id="337" Count="0" />
<LineId Id="342" Count="1" />
<LineId Id="345" Count="2" />
<LineId Id="344" Count="0" />
<LineId Id="349" Count="0" />
<LineId Id="348" Count="0" />
<LineId Id="350" Count="1" />
<LineId Id="12" Count="275" />
<LineId Id="317" Count="2" />
<LineId Id="326" Count="0" />
<LineId Id="325" Count="0" />
<LineId Id="327" Count="1" />
<LineId Id="330" Count="0" />
<LineId Id="329" Count="0" />
<LineId Id="331" Count="1" />
<LineId Id="334" Count="0" />
<LineId Id="333" Count="0" />
<LineId Id="335" Count="1" />
<LineId Id="322" Count="0" />
<LineId Id="321" Count="0" />
<LineId Id="323" Count="1" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Module.FB_init">
<LineId Id="3" Count="13" />
<LineId Id="18" Count="0" />
<LineId Id="21" Count="1" />
<LineId Id="19" Count="1" />
<LineId Id="17" Count="0" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Module.Name.Get">
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Module.Name.Set">
<LineId Id="3" Count="8" />
<LineId Id="2" Count="0" />
<LineId Id="14" Count="0" />
<LineId Id="13" Count="0" />
<LineId Id="12" Count="0" />
</LineIds>
</POU>
</TcPlcObject>

View File

@@ -54,6 +54,7 @@ VAR_INPUT
// String inverter ip
sInverterIP : STRING;
xECStateSCS AT %I* : UINT;
END_VAR
VAR_OUTPUT
// Current string voltage
@@ -130,6 +131,9 @@ VAR
// DC Main switch not closed
_fbDCMainSwitchNotClosed : FB_TcAlarm;
// Connection to SCS lost
_fbSCSConnLost : FB_TcAlarm;
// Shutdown discharge stopped messages
_fbSDDCLevel : FB_TcMessage;
_fbSDUnitThreshold : FB_TcMessage;
@@ -206,6 +210,21 @@ xAllModulesInAutoMode := TRUE;
// Reset Safety
xResetSafetyDCCB := xResetSafety;
// ===============================
// EtherCAT connection lost error handling
// ===============================
IF (xECStateSCS <> 8) AND (NOT _fbSCSConnLost.bRaised) AND xReleaseErrors THEN
_fbSCSConnLost.Raise(0);
END_IF
IF (xECStateSCS = 8) AND _fbSCSConnLost.bRaised THEN
_fbSCSConnLost.Clear(0, FALSE);
END_IF
IF _fbSCSConnLost.eConfirmationState = TcEventConfirmationState.WaitForConfirmation AND xConfirmAlarms THEN
_fbSCSConnLost.Confirm(0);
END_IF
// ===============================
// DC Main switch error handling
// ===============================
@@ -532,6 +551,7 @@ CASE _iState OF
20: // Check if DC relais closed and safety is ok
IF NOT xDCCBOpen THEN
_tonErrorDCCBNotClosed.IN := FALSE;
_xEnableInverter := TRUE;
_rPowerInverterInternal := rPowerInverter;
//_rPowerInverterInternal := 0.0;
@@ -565,13 +585,18 @@ CASE _iState OF
_rPowerInverterInternal := 0.0;
_xEnable := FALSE;
_iState := 31;
_tonInverterStartupTimeout(IN := FALSE);
END_IF
// Inverter error or timeout for startup
IF _fbInverter.xError OR (NOT xRepairSwitchOk) THEN // _tonInverterStartupTimeout.Q
IF _fbInverter.xError OR (NOT xRepairSwitchOk) OR _tonInverterStartupTimeout.Q THEN // _tonInverterStartupTimeout.Q
// Shutdown beacause of inverter startup timeout
IF _tonInverterStartupTimeout.Q AND (NOT _fbInverterStartupTimeoutAlarm.bRaised) THEN
_fbInverterStartupTimeoutAlarm.Raise(0);
END_IF
_iState := 1000;
_xEnableInverter := FALSE;
xError := TRUE;
@@ -650,8 +675,8 @@ CASE _iState OF
// Restart on Enable or StartBalancing
IF xEnable OR xStartBalancing THEN
_rPowerInverterInternal := 0.0;
_xEnableInverter := FALSE;
_iState := 40;
//_xEnableInverter := FALSE;
_iState := 0;
END_IF
40: // Wait for inverter to shut down
@@ -750,6 +775,9 @@ VAR_INPUT
sName : STRING;
END_VAR
VAR
_sTemp : STRING;
END_VAR
]]></Declaration>
<Implementation>
<ST><![CDATA[_sName := sName;
@@ -775,6 +803,11 @@ _fbInverterStartupTimeoutAlarm.ipArguments.Clear().AddString(_sName);
_fbDCMainSwitchNotClosed.CreateEx(stEventEntry := TC_EVENTS.General.DCMainSwitchNotClosed, bWithConfirmation := FALSE, 0);
_fbDCMainSwitchNotClosed.ipArguments.Clear().AddString(_sName);
// EtherCAT communication lost alarm
_fbSCSConnLost.CreateEx(stEventEntry := TC_EVENTS.General.CommError, bWithConfirmation := TRUE, 0);
_sTemp := CONCAT(_sName, ' SCS');
_fbSCSConnLost.ipArguments.Clear().AddString(_sTemp);
// Shutdown discharge messages
_fbSDDCLevel.CreateEx(TC_EVENTS.BMSEvents.SDDCVoltage, 0);
_fbSDDCLevel.ipArguments.Clear().AddString(_sName);
@@ -805,6 +838,9 @@ _fbModule1.Name := CONCAT(_sName, ' - Module 1');
_fbModule2.Name := CONCAT(_sName, ' - Module 2');
_fbModule3.Name := CONCAT(_sName, ' - Module 3');
// Set inverter Name
_fbInverter.Name := _sName;
// Create alarm messages
_fbModulesOutOfBalanceAlarm.ipArguments.Clear().AddString(_sName);
_fbSafetyInterlocksNotOkAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
@@ -812,18 +848,47 @@ _fbSafetyInterlocksNotOkAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
</Set>
</Property>
<LineIds Name="FB_String">
<LineId Id="3" Count="542" />
<LineId Id="3" Count="7" />
<LineId Id="600" Count="2" />
<LineId Id="599" Count="0" />
<LineId Id="603" Count="2" />
<LineId Id="607" Count="0" />
<LineId Id="606" Count="0" />
<LineId Id="608" Count="1" />
<LineId Id="611" Count="0" />
<LineId Id="610" Count="0" />
<LineId Id="612" Count="1" />
<LineId Id="11" Count="326" />
<LineId Id="597" Count="0" />
<LineId Id="338" Count="32" />
<LineId Id="578" Count="0" />
<LineId Id="371" Count="0" />
<LineId Id="582" Count="0" />
<LineId Id="584" Count="0" />
<LineId Id="372" Count="2" />
<LineId Id="587" Count="2" />
<LineId Id="377" Count="0" />
<LineId Id="596" Count="0" />
<LineId Id="378" Count="167" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_String.FB_init">
<LineId Id="3" Count="27" />
<LineId Id="3" Count="21" />
<LineId Id="31" Count="2" />
<LineId Id="35" Count="0" />
<LineId Id="34" Count="0" />
<LineId Id="25" Count="5" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_String.Name.Get">
<LineId Id="1" Count="0" />
</LineIds>
<LineIds Name="FB_String.Name.Set">
<LineId Id="1" Count="9" />
<LineId Id="1" Count="5" />
<LineId Id="12" Count="0" />
<LineId Id="11" Count="0" />
<LineId Id="13" Count="0" />
<LineId Id="7" Count="3" />
</LineIds>
</POU>
</TcPlcObject>

View File

@@ -1,5 +1,5 @@
<?xml version="1.0" encoding="utf-8"?>
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.7">
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.8">
<POU Name="FB_Unit" Id="{e9bb815b-eb46-4920-800d-910484e58b22}" SpecialFunc="None">
<Declaration><![CDATA[FUNCTION_BLOCK FB_Unit
VAR_INPUT
@@ -45,12 +45,13 @@ VAR_INPUT
// Switch all components to manual mode
xAllToManualMode : BOOL;
// Switch all components to auto mode
// Inverter enabled status
xInverterEnabled : BOOL;
END_VAR
VAR_OUTPUT
// Unit state
eUnitState : E_COMPONENT_STATUS := E_COMPONENT_STATUS.OFF;
// Unit ready
xReady : BOOL;
@@ -778,6 +779,7 @@ CASE _iState OF
_xReleaseManualMode := FALSE;
_timUnitStartupWaitTime := GVL_CONFIG.timUnitStartupTime;
_iState := 10;
eUnitState := E_COMPONENT_STATUS.STARTING;
END_IF
IF (NOT xEnable) AND xStartBalancing AND _xAllComponentsInAutomatic AND (NOT _xErrorActive) THEN
@@ -867,6 +869,7 @@ CASE _iState OF
// Continue on normal startup path
IF xEnable THEN
eUnitState := E_COMPONENT_STATUS.ON;
_iState := 35;
END_IF
@@ -888,6 +891,7 @@ CASE _iState OF
_rSetpointPosolytPumpInlet := GVL_CONFIG.rPumpPosolytOnPower;
IF (NOT xEnable) THEN
eUnitState := E_COMPONENT_STATUS.SHUTDOWN;
_iState := 40;
END_IF
@@ -971,12 +975,14 @@ CASE _iState OF
xOff := TRUE;
_xReleaseManualMode := TRUE;
IF NOT _xErrorActive THEN
eUnitState := E_COMPONENT_STATUS.OFF;
_iState := 0;
END_IF
END_IF
// Check for restart condition
IF xEnable AND (NOT _xErrorActive) THEN
eUnitState := E_COMPONENT_STATUS.OFF;
_iState := 0;
END_IF
@@ -1065,6 +1071,7 @@ CASE _iState OF
1000: // Error shutdown
eUnitState := E_COMPONENT_STATUS.ERROR;
_fbNegolytValveTankOutlet.ReqAutomaticClose();
_fbPosolytValveTankOutlet.ReqAutomaticClose();
_fbPosolytPumpInlet.ReqAutomaticStop();
@@ -1082,10 +1089,41 @@ CASE _iState OF
// automatic restart of the unit
IF (NOT _xErrorActive) AND (NOT xEnable) AND (NOT xStartBalancing) AND xConfirmAlarms THEN
xError := FALSE;
_iState := 0;
_iState := 51;
END_IF
END_CASE]]></ST>
</Implementation>
</Action>
<LineIds Name="FB_Unit">
<LineId Id="3" Count="498" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Unit.FB_init">
<LineId Id="3" Count="7" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Unit.Name.Get">
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Unit.Name.Set">
<LineId Id="3" Count="2" />
<LineId Id="2" Count="0" />
</LineIds>
<LineIds Name="FB_Unit.StateMachine">
<LineId Id="2" Count="8" />
<LineId Id="317" Count="0" />
<LineId Id="11" Count="88" />
<LineId Id="318" Count="0" />
<LineId Id="100" Count="20" />
<LineId Id="319" Count="0" />
<LineId Id="121" Count="82" />
<LineId Id="321" Count="0" />
<LineId Id="204" Count="5" />
<LineId Id="322" Count="0" />
<LineId Id="210" Count="87" />
<LineId Id="323" Count="0" />
<LineId Id="298" Count="18" />
<LineId Id="1" Count="0" />
</LineIds>
</POU>
</TcPlcObject>

View File

@@ -1,5 +1,5 @@
<?xml version="1.0" encoding="utf-8"?>
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4024.12">
<TcPlcObject Version="1.1.0.1" ProductVersion="3.1.4026.8">
<POU Name="FB_PowerSupplySunspec" Id="{a826dd09-442c-45c5-8ae3-9b71f293003c}" SpecialFunc="None">
<Declaration><![CDATA[FUNCTION_BLOCK FB_PowerSupplySunspec
VAR_INPUT
@@ -216,6 +216,11 @@ END_IF
CASE _iState OF
0: // Off
IF _tonPollingTimer.Q THEN
_tonPollingTimer(IN := FALSE, PT := _timPollingDelay);
_iState := 1;
END_IF
// If enable and INTLK Ok
IF xEnable THEN
_iState := 10;
@@ -224,10 +229,7 @@ CASE _iState OF
_tonPollingTimer(IN := TRUE, PT := _timPollingDelay);
END_IF
IF _tonPollingTimer.Q THEN
_tonPollingTimer(IN := FALSE, PT := _timPollingDelay);
_iState := 1;
END_IF
1: // Read inverter status
@@ -485,6 +487,7 @@ CASE _iState OF
_iState := 25;
// Check for valid value
IF (_iWMaxSF < -10) OR (_iWMaxSF > 10) OR (_iWMaxSF = 16#8000) THEN
ADSLOGSTR(msgCtrlMask := ADSLOG_MSGTYPE_HINT, msgFmtStr := 'FBInverter into error state from: %s', strArg := TO_STRING(_iState));
// Goto error state
_iState := 1000;
END_IF
@@ -1190,17 +1193,41 @@ _fbErrorInverterAlarm.CreateEx(stEventEntry := TC_EVENTS.Inverter.InverterError,
_fbErrorInverterAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
</Implementation>
</Method>
<Property Name="Name" Id="{ef8c6e8f-7c1b-4781-b201-87f759acb289}">
<Declaration><![CDATA[PROPERTY Name : string]]></Declaration>
<Get Name="Get" Id="{bc17161e-727d-4abd-a845-a7eacc08f995}">
<Declaration><![CDATA[VAR
END_VAR
]]></Declaration>
<Implementation>
<ST><![CDATA[Name := _sName;]]></ST>
</Implementation>
</Get>
<Set Name="Set" Id="{7fdecf53-efe5-43de-bc46-5f24fb6a7ffb}">
<Declaration><![CDATA[VAR
END_VAR
]]></Declaration>
<Implementation>
<ST><![CDATA[_sName := Name;
_fbErrorInverterAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
</Implementation>
</Set>
</Property>
<LineIds Name="FB_PowerSupplySunspec">
<LineId Id="774" Count="10" />
<LineId Id="1550" Count="0" />
<LineId Id="785" Count="3" />
<LineId Id="785" Count="0" />
<LineId Id="4104" Count="2" />
<LineId Id="4103" Count="0" />
<LineId Id="4107" Count="0" />
<LineId Id="786" Count="2" />
<LineId Id="2615" Count="0" />
<LineId Id="790" Count="0" />
<LineId Id="2614" Count="0" />
<LineId Id="2613" Count="0" />
<LineId Id="2616" Count="1" />
<LineId Id="2906" Count="0" />
<LineId Id="2618" Count="2" />
<LineId Id="2616" Count="0" />
<LineId Id="2619" Count="1" />
<LineId Id="3661" Count="0" />
<LineId Id="2621" Count="0" />
<LineId Id="2623" Count="15" />
@@ -1262,7 +1289,9 @@ _fbErrorInverterAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
<LineId Id="1725" Count="0" />
<LineId Id="1721" Count="0" />
<LineId Id="1433" Count="0" />
<LineId Id="816" Count="28" />
<LineId Id="816" Count="24" />
<LineId Id="4096" Count="0" />
<LineId Id="841" Count="3" />
<LineId Id="1171" Count="0" />
<LineId Id="845" Count="5" />
<LineId Id="3656" Count="0" />
@@ -1429,5 +1458,11 @@ _fbErrorInverterAlarm.ipArguments.Clear().AddString(_sName);]]></ST>
<LineId Id="11" Count="0" />
<LineId Id="7" Count="1" />
</LineIds>
<LineIds Name="FB_PowerSupplySunspec.Name.Get">
<LineId Id="1" Count="0" />
</LineIds>
<LineIds Name="FB_PowerSupplySunspec.Name.Set">
<LineId Id="1" Count="2" />
</LineIds>
</POU>
</TcPlcObject>

View File

@@ -270,7 +270,7 @@
</System>
<Plc>
<Project GUID="{9AE64910-5EB2-4866-93FD-EFE059C38C36}" Name="PLC" PrjFilePath="PLC\PLC.plcproj" TmcFilePath="PLC\PLC.tmc" ReloadTmc="true" AmsPort="851" FileArchiveSettings="#x000e" CopyTmcToTarget="true" CopyTpyToTarget="false" SymbolicMapping="true">
<Instance Id="#x08502000" TcSmClass="TComPlcObjDef" KeepUnrestoredLinks="2" TmcHash="{3746FC02-B3A8-434D-F26F-358D6D1B8911}" TmcPath="PLC\PLC.tmc">
<Instance Id="#x08502000" TcSmClass="TComPlcObjDef" KeepUnrestoredLinks="2" TmcHash="{787BDD68-3E05-D656-2CBB-66298A3E185C}" TmcPath="PLC\PLC.tmc">
<Name>PLC Instance</Name>
<CLSID ClassFactory="TcPlc30">{08500001-0000-0000-F000-000000000064}</CLSID>
<Vars VarGrpType="2" AreaNo="1">
@@ -279,6 +279,19 @@
<Name>MAIN._xShowAckEmergencyStop</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN.xSafetyRun</Name>
<Comment><![CDATA[ Safety]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN.xSafetyErrAck</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._xShowErrorOnButton</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0].xCloseDCCB</Name>
<Comment><![CDATA[ Signal to close dc circuit breaker]]></Comment>
@@ -1283,19 +1296,6 @@
<Comment><![CDATA[ Motor speed setpoint]]></Comment>
<Type>INT</Type>
</Var>
<Var>
<Name>MAIN.xSafetyRun</Name>
<Comment><![CDATA[ Safety]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN.xSafetyErrAck</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._xShowErrorOnButton</Name>
<Type>BOOL</Type>
</Var>
</Vars>
<Vars VarGrpType="1">
<Name>PlcTask Inputs</Name>
@@ -1307,6 +1307,32 @@
<Name>MAIN._xString1DCSafetyOk</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN.xSafetyResterTaster</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._xHarwareResetButton</Name>
<Comment><![CDATA[ Hardware reset button]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._uiEtherCATState</Name>
<Comment><![CDATA[ String EtherCAT state]]></Comment>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._fbSafety.xVoltagesInRange</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._fbSafety.xPressureInRange</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._fbSafety.xTemperaturesInRange</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0].xSafetyIntlksOk</Name>
<Comment><![CDATA[ All safetyinterlocks from safety plc are ok]]></Comment>
@@ -1322,6 +1348,10 @@
<Comment><![CDATA[ Repair switch closed]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0].xECStateSCS</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0].xDCCBOpen</Name>
<Comment><![CDATA[ Signal that dc circuit breakers are closed]]></Comment>
@@ -1342,6 +1372,10 @@
<Comment><![CDATA[ Leakage tank]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0]._fbModule1.xECState</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0]._fbModule1._fbUnit1._fbPosolytValveTankOutlet.xOpenFeedback</Name>
<Type>BOOL</Type>
@@ -2249,6 +2283,10 @@
<Comment><![CDATA[ Leakage tank]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0]._fbModule2.xECState</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0]._fbModule2._fbUnit1._fbPosolytValveTankOutlet.xOpenFeedback</Name>
<Type>BOOL</Type>
@@ -3156,6 +3194,10 @@
<Comment><![CDATA[ Leakage tank]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0]._fbModule3.xECState</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[0]._fbModule3._fbUnit1._fbPosolytValveTankOutlet.xOpenFeedback</Name>
<Type>BOOL</Type>
@@ -4084,6 +4126,10 @@
<Comment><![CDATA[ Repair switch closed]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1].xECStateSCS</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1].xDCCBOpen</Name>
<Comment><![CDATA[ Signal that dc circuit breakers are closed]]></Comment>
@@ -4104,6 +4150,10 @@
<Comment><![CDATA[ Leakage tank]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1]._fbModule1.xECState</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1]._fbModule1._fbUnit1._fbPosolytValveTankOutlet.xOpenFeedback</Name>
<Type>BOOL</Type>
@@ -5011,6 +5061,10 @@
<Comment><![CDATA[ Leakage tank]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1]._fbModule2.xECState</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1]._fbModule2._fbUnit1._fbPosolytValveTankOutlet.xOpenFeedback</Name>
<Type>BOOL</Type>
@@ -5918,6 +5972,10 @@
<Comment><![CDATA[ Leakage tank]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1]._fbModule3.xECState</Name>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._afbStrings[1]._fbModule3._fbUnit1._fbPosolytValveTankOutlet.xOpenFeedback</Name>
<Type>BOOL</Type>
@@ -6831,32 +6889,6 @@
EL30xx also sets this if an underrange or overrange error is present]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN.xSafetyResterTaster</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._xHarwareResetButton</Name>
<Comment><![CDATA[ Hardware reset button]]></Comment>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._uiEtherCATState</Name>
<Comment><![CDATA[ String EtherCAT state]]></Comment>
<Type>UINT</Type>
</Var>
<Var>
<Name>MAIN._fbSafety.xVoltagesInRange</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._fbSafety.xPressureInRange</Name>
<Type>BOOL</Type>
</Var>
<Var>
<Name>MAIN._fbSafety.xTemperaturesInRange</Name>
<Type>BOOL</Type>
</Var>
</Vars>
<Contexts>
<Context>
@@ -44085,6 +44117,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)">
<Link VarA="PlcTask Inputs^MAIN._uiEtherCATState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^-10K1 X1 SCS S1 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0].xECStateSCS" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^-10K1 X1 SCS S1 (EK1100)^=STRNG01-11K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0].xRepairSwitchOk" VarB="Channel 3^DC Trennschalter OK"/>
</OwnerB>
@@ -44100,6 +44135,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Outputs^MAIN.xSafetyErrAck" VarB="StandardOutputs^LocalSafety.ErrAck_63"/>
<Link VarA="PlcTask Outputs^MAIN.xSafetyRun" VarB="StandardOutputs^LocalSafety.Run_62"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^-10K1 X1 SCS S2 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1].xECStateSCS" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^-10K1 X1 SCS S2 (EK1100)^=STRNG02-11K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1].xRepairSwitchOk" VarB="Channel 3^DC TRennschalter OK"/>
</OwnerB>
@@ -44115,6 +44153,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Outputs^MAIN.xSafetyErrAck" VarB="StandardOutputs^LocalSafety.ErrAck_63"/>
<Link VarA="PlcTask Outputs^MAIN.xSafetyRun" VarB="StandardOutputs^LocalSafety.Run_62"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S1M1 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule1.xECState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S1M1 (EK1100)^=STRNG01++BATMOD01-30K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule1._fbUnit1._fbNegolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback Unit 1"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule1._fbUnit1._fbPosolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback Unit 1"/>
@@ -44349,6 +44390,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule1._fbUnit4._fbTempSensorPosolyt.xOverrange" VarB="RTD Inputs Channel 4^Status^Overrange"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule1._fbUnit4._fbTempSensorPosolyt.xUnderrange" VarB="RTD Inputs Channel 4^Status^Underrange"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S1M2 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule2.xECState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S1M2 (EK1100)^=STRNG01++BATMOD02-30K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule2._fbUnit1._fbNegolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule2._fbUnit1._fbPosolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
@@ -44581,6 +44625,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule2._fbUnit4._fbTempSensorPosolyt.xOverrange" VarB="RTD Inputs Channel 4^Status^Overrange"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule2._fbUnit4._fbTempSensorPosolyt.xUnderrange" VarB="RTD Inputs Channel 4^Status^Underrange"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S1M3 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule3.xECState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S1M3 (EK1100)^=STRNG01++BATMOD03-30K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule3._fbUnit1._fbNegolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule3._fbUnit1._fbPosolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
@@ -44813,6 +44860,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule3._fbUnit4._fbTempSensorPosolyt.xOverrange" VarB="RTD Inputs Channel 4^Status^Overrange"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[0]._fbModule3._fbUnit4._fbTempSensorPosolyt.xUnderrange" VarB="RTD Inputs Channel 4^Status^Underrange"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S2M1 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule1.xECState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S2M1 (EK1100)^=STRNG02++BATMOD01-30K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule1._fbUnit1._fbNegolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule1._fbUnit1._fbPosolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
@@ -45047,6 +45097,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule1._fbUnit4._fbTempSensorPosolyt.xOverrange" VarB="RTD Inputs Channel 4^Status^Overrange"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule1._fbUnit4._fbTempSensorPosolyt.xUnderrange" VarB="RTD Inputs Channel 4^Status^Underrange"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S2M2 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule2.xECState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S2M2 (EK1100)^=STRNG02++BATMOD02-30K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule2._fbUnit1._fbNegolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule2._fbUnit1._fbPosolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
@@ -45281,6 +45334,9 @@ Bit1: Value smaller than Limit2]]></Comment>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule2._fbUnit4._fbTempSensorPosolyt.xOverrange" VarB="RTD Inputs Channel 4^Status^Overrange"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule2._fbUnit4._fbTempSensorPosolyt.xUnderrange" VarB="RTD Inputs Channel 4^Status^Underrange"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S2M3 (EK1100)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule3.xECState" VarB="InfoData^State"/>
</OwnerB>
<OwnerB Name="TIID^X103 (EtherCAT)^-41K1 (EK1100)^-47K1 (EK1122)^S2M3 (EK1100)^=STRNG02++BATMOD03-30K1 (EL1018)">
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule3._fbUnit1._fbNegolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>
<Link VarA="PlcTask Inputs^MAIN._afbStrings[1]._fbModule3._fbUnit1._fbPosolytPumpInlet.xMCBOk" VarB="Channel 7^EFuse -12F2 Sum Feedback"/>

View File

@@ -2,7 +2,7 @@
<TcModuleClass>
<DataTypes>
<DataType>
<Name GUID="{BD0D8994-D42B-4E02-BE24-29FD5E93E224}">General</Name>
<Name GUID="{B7B78A52-E90B-4F37-BCAB-7CA0B0A3EDAA}">General</Name>
<DisplayName TxtId=""><![CDATA[General alarms and infos]]></DisplayName>
<EventId>
<Name Id="1">NotAllCompInAutomatic</Name>
@@ -39,6 +39,11 @@
<DisplayName TxtId=""><![CDATA[{0}: Leakage in tank]]></DisplayName>
<Severity>Error</Severity>
</EventId>
<EventId>
<Name Id="8">CommError</Name>
<DisplayName TxtId=""><![CDATA[{0}: EtherCAT communication error]]></DisplayName>
<Severity>Error</Severity>
</EventId>
<Hides>
<Hide GUID="{2AC7C19C-D057-4107-A9DC-D12E37F9C437}"/>
<Hide GUID="{B2B1693C-04F1-434F-9927-39B63A3B2C0A}"/>
@@ -51,6 +56,7 @@
<Hide GUID="{677C8DA2-F584-470D-8DAC-E02B6811C1C6}"/>
<Hide GUID="{3D3A6A26-888D-43BE-A325-480AA7F2885F}"/>
<Hide GUID="{14064F83-69AA-4308-B296-55948A63182D}"/>
<Hide GUID="{BD0D8994-D42B-4E02-BE24-29FD5E93E224}"/>
</Hides>
</DataType>
<DataType>
@@ -133,7 +139,7 @@
</Hides>
</DataType>
<DataType>
<Name GUID="{2B097BE6-5FA1-4489-9C48-249D306057A8}">Inverter</Name>
<Name GUID="{A81DA913-2653-4965-B95F-B789E5F910DF}">Inverter</Name>
<DisplayName TxtId=""><![CDATA[Inverter events]]></DisplayName>
<EventId>
<Name Id="1">InverterOverTemp</Name>
@@ -177,7 +183,7 @@
</EventId>
<EventId>
<Name Id="9">InverterError</Name>
<DisplayName TxtId=""><![CDATA[{} inverter Error]]></DisplayName>
<DisplayName TxtId=""><![CDATA[{0}: Inverter Error]]></DisplayName>
<Severity>Error</Severity>
</EventId>
<Hides>
@@ -191,6 +197,7 @@
<Hide GUID="{5C6886CF-C5BA-4DED-87EF-6E443F06D6E2}"/>
<Hide GUID="{86A2A820-4D64-4C1F-87D8-07667F4EA902}"/>
<Hide GUID="{71BB472B-94DE-4D07-A2C4-A75D33C5049A}"/>
<Hide GUID="{2B097BE6-5FA1-4489-9C48-249D306057A8}"/>
</Hides>
</DataType>
</DataTypes>