19 Commits

Author SHA1 Message Date
Matthias Heisig
2d65d0b3db Last changes before SAT 2025-10-14 16:19:19 +02:00
Matthias Heisig
698451cc1f Some bugfixes
- Config for max string power is now correctly calculated
- Adjusted timing for string and inverter timeout
2025-09-29 11:38:43 +02:00
Matthias Heisig
dd82744356 Fixed some bugs and added inverter status to modbus register
- Safety now has a tof of 0,5s for Temp, Voltage and Pressure
- Doppelhöcker now switches powercommand during second phase
2025-09-24 10:10:37 +02:00
Matthias Heisig
d882effb35 Modified safety for better alarm messages and cleaned up 2025-09-12 16:07:02 +02:00
Markus.Neukirch
f0e6143997 IBN changes
added sync units for cabinet temperature, changes in modbus interface to EMS (1.0.4 and 1.0.5), added error counter to modbus communication, lot of changes to kaco (faults, consecutive errors, bms error messages), isolation error ledge, allowed startbalancing when on shutdown, tower light integration
2025-09-05 14:24:37 +02:00
Markus Neukirch
6f97c1aa6b Safety EStop Changes
added SCS EStop to FSOE connection to main safety and it's evaluation
2025-08-05 17:16:25 +02:00
Matthias Heisig
58f3c751d3 Some fixes before the FAT
- Refactored inverter Heartbeat check
- Added SafetyComError on EtherCAT checking
- Adjusted lower pressure value for safety plc from 200 mBar to 300mBar
2025-06-06 19:09:12 +02:00
Matthias Heisig
f12063e294 Added some fixed during pre safety check
- Fixed bug that SafetyIntlkTimeout could not be acknowledged
- Pumps now dont shut off during error in unit (except over- or underpressure), setpoint is now set to discharge power
- Fixed bug not able to restart safety-check when not all strings where off
- Adjusted Safetyparameters to match safetycheck protocol
2025-06-03 18:02:19 +02:00
Matthias Heisig
2f9f4df261 changes during start of safety check
- Refactoring of string fb
- Added pump safety interlocks for pressure segment inlet too low and too high
2025-06-02 19:51:57 +02:00
Matthias Heisig
94381dc704 Changed Safety program so that every group can be deactivated 2025-04-28 17:15:43 +02:00
Matthias Heisig
2221f6bab3 Minor bugfixes and future addons 2025-04-06 10:21:01 +02:00
Matthias Heisig
2ded890dd4 Added multi string handling and balancing 2025-02-13 21:26:50 +01:00
Matthias Heisig
f9df0a5180 Added precharging to SafetyCheck 2025-02-10 08:44:52 +01:00
Matthias Heisig
58e511438e Umstellung auf TwinCAT 4026 2024-07-29 07:33:50 +02:00
Matthias Heisig
0d9a4d9c72 WIP: Aktueller stand für fehlersuche Sensorrauschen 2024-05-22 17:43:26 +02:00
Matthias Heisig
327f324be8 Implemented fixes and improvements during comissioning
- New Balancing mode
- HMI Interface for Inverterdata implemented
- Adjusted GVL_CONFIG values
- Read inverter data even when inverter is off
- Added OPC UA settings to inverter data hmi interface
- Added multisettings to safety project for strings
2024-05-06 11:05:33 +02:00
Matthias Heisig
b95033a155 First string implemented 2024-04-18 08:32:21 +02:00
Matthias Heisig
9ce3522a70 WIP: Inbetriebnahme vorladen 2024-04-11 19:06:45 +02:00
Matthias Heisig
ef26159a4f Added safety program pre comissioning and started implementing different modes 2024-03-20 18:08:57 +01:00