added sync units for cabinet temperature, changes in modbus interface to EMS (1.0.4 and 1.0.5), added error counter to modbus communication, lot of changes to kaco (faults, consecutive errors, bms error messages), isolation error ledge, allowed startbalancing when on shutdown, tower light integration
- Refactored inverter Heartbeat check
- Added SafetyComError on EtherCAT checking
- Adjusted lower pressure value for safety plc from 200 mBar to 300mBar
- Fixed bug that SafetyIntlkTimeout could not be acknowledged
- Pumps now dont shut off during error in unit (except over- or underpressure), setpoint is now set to discharge power
- Fixed bug not able to restart safety-check when not all strings where off
- Adjusted Safetyparameters to match safetycheck protocol
- Iso error in string will now only be active if the dc circuit breaker is not closed
- Added some delay between closing dc circuit breaker and enabling inverter so that the dc bus voltage can stabilize itself
- New Balancing mode
- HMI Interface for Inverterdata implemented
- Adjusted GVL_CONFIG values
- Read inverter data even when inverter is off
- Added OPC UA settings to inverter data hmi interface
- Added multisettings to safety project for strings