Matthias Heisig
eaaa2371e8
Change E-Stop so that it can also work with one string
...
- Also optimized CV charging
2025-10-07 16:23:37 +02:00
Matthias Heisig
26d602eafc
Added possibility to charge with cv
2025-10-01 10:45:51 +02:00
Matthias Heisig
698451cc1f
Some bugfixes
...
- Config for max string power is now correctly calculated
- Adjusted timing for string and inverter timeout
2025-09-29 11:38:43 +02:00
Matthias Heisig
02dddfc41a
Adjusted analog input limits and delays
...
- Adjusted analog input warnings and delays to match safety program levels
2025-09-12 11:11:50 +02:00
Matthias Heisig
8bd2e9a1ea
Added inverter startup timeout to GVL_CONFIG and enabled inverter errors
2025-09-11 16:32:53 +02:00
Markus.Neukirch
f0e6143997
IBN changes
...
added sync units for cabinet temperature, changes in modbus interface to EMS (1.0.4 and 1.0.5), added error counter to modbus communication, lot of changes to kaco (faults, consecutive errors, bms error messages), isolation error ledge, allowed startbalancing when on shutdown, tower light integration
2025-09-05 14:24:37 +02:00
Markus Neukirch
e2a44b0d37
Added cabinet temperature and modbus registers
...
added cabinet temperature to each module, scs and bms cabinet, added corresponding config, hmi interface, hardware & links. Added corresponding warning bits to modbus registers
2025-08-04 18:10:15 +02:00
Matthias Heisig
e6802b87b4
Changes after BMS EMS connection test with uniper
...
- Added EMS heartbeat timeout
- Removed commented code
- Fixed BMS Error DC-Switch: Was true when switch was ok and vice versa
2025-06-19 19:10:26 +02:00
Matthias Heisig
b6791f7951
Small changes after FAT and EMS Test
...
- Changed Modbus server config for EMS connectivity
- Changed some default EWL Limits
2025-06-13 16:37:14 +02:00
Matthias Heisig
ac0a8d160b
Change in startup time for Doppelhöckertest
...
- Was 1 Minute, is now 5 seconds
2025-06-02 19:49:50 +02:00
Matthias Heisig
70090f08d9
Single strings can now be activated or deactivated
2025-04-28 17:14:17 +02:00
Matthias Heisig
7b810b19d2
Implemented a better balancing algorith for string balancing
...
* Added error logging to inverter fb
* Changed HMI actual power feedback from dc to ac power
* Small config adjustments
2025-04-16 12:35:06 +02:00
Matthias Heisig
4a00a4c414
Added Modbus registers
2025-04-08 07:24:55 +02:00
Matthias Heisig
2221f6bab3
Minor bugfixes and future addons
2025-04-06 10:21:01 +02:00
Matthias Heisig
2ded890dd4
Added multi string handling and balancing
2025-02-13 21:26:50 +01:00
Matthias Heisig
f9df0a5180
Added precharging to SafetyCheck
2025-02-10 08:44:52 +01:00
Matthias Heisig
39a02352f6
Iso and leackage error messages added
2024-09-10 16:54:17 +02:00
Matthias Heisig
08d2ffd136
Added string startup timeout
2024-08-30 13:12:42 +02:00
Matthias Heisig
0d9a4d9c72
WIP: Aktueller stand für fehlersuche Sensorrauschen
2024-05-22 17:43:26 +02:00
Matthias Heisig
0ffff9be2a
EMS communication and Voltage optimizations
...
- Added data for EMS communication
- Added highest segment voltage for charging check
- Added lowest segment voltage for discharging check
2024-05-07 17:10:29 +02:00
Matthias Heisig
327f324be8
Implemented fixes and improvements during comissioning
...
- New Balancing mode
- HMI Interface for Inverterdata implemented
- Adjusted GVL_CONFIG values
- Read inverter data even when inverter is off
- Added OPC UA settings to inverter data hmi interface
- Added multisettings to safety project for strings
2024-05-06 11:05:33 +02:00
Matthias Heisig
b95033a155
First string implemented
2024-04-18 08:32:21 +02:00
Matthias Heisig
9ce3522a70
WIP: Inbetriebnahme vorladen
2024-04-11 19:06:45 +02:00
Matthias Heisig
ef26159a4f
Added safety program pre comissioning and started implementing different modes
2024-03-20 18:08:57 +01:00
Matthias Heisig
57987cb19f
Fixed Modbus register access
2024-01-17 11:26:11 +01:00
Matthias Heisig
4586e72a0e
Added inverter implementation
2024-01-05 16:27:39 +01:00
Matthias Heisig
faa33db290
Projektdateien hinzufügen.
2024-01-04 15:15:26 +01:00