- Fixed bug that SafetyIntlkTimeout could not be acknowledged
- Pumps now dont shut off during error in unit (except over- or underpressure), setpoint is now set to discharge power
- Fixed bug not able to restart safety-check when not all strings where off
- Adjusted Safetyparameters to match safetycheck protocol
- Iso error in string will now only be active if the dc circuit breaker is not closed
- Added some delay between closing dc circuit breaker and enabling inverter so that the dc bus voltage can stabilize itself
- New Balancing mode
- HMI Interface for Inverterdata implemented
- Adjusted GVL_CONFIG values
- Read inverter data even when inverter is off
- Added OPC UA settings to inverter data hmi interface
- Added multisettings to safety project for strings