| 1 | Start Adresse | Größe (WORD) | Name | Typ | EMS Access | BMS Access | Einheit | Beschreibung | Kommentar |
|---|---|---|---|---|---|---|---|---|---|
| 2 | 10000 | 16 | Manufacturer | ASCII | R | RW | Batterie Hersteller Name | ||
| 3 | 10016 | 16 | Modell Name | ASCII | R | RW | Batterie Modell | ||
| 4 | 10032 | 16 | Serial Number | ASCII | R | RW | Batterie Seriennummer | ||
| 5 | 10048 | 32 | BMS Version | ASCII | R | RW | BMS Version | ||
| 6 | 10080 | 1 | Total Parallel Members | UINT16 | R | RW | Anzahl aller parallel verschalteten Strings | ||
| 7 | 10081 | 1 | Active Parallel Members | UINT16 | R | RW | Anzahl der aktuell aktiven parallel veschalteten Strings | ||
| 8 | 11000 | 1 | Battery Status | ENUM16 | R | RW | Batterie Status (Siehe 'Enum & Bitmap Values') | ||
| 9 | 11001 | 1 | Charge Status | ENUM16 | R | RW | Lade Status (Possible values in the table 'Enum & Bitmap Values') | ||
| 10 | 11002 | 1 | Self discharge rate | UINT16 | R | RW | % | Selbstentladerate in Prozent der gesamtkapazität (WHRtg) pro Tag | Nicht implementiert |
| 11 | 11003 | 1 | Max allowed SoC | UINT16 | R | RW | % | Maximaler SoC in abhägigkeit der gerade verwendeten Ladeleistung | Nicht implementiert |
| 12 | 11004 | 1 | Min allowed SoC | UINT16 | R | RW | % | Minimaler SoC in abhägigkeit der gerade verwendeten Entladeleistung | Nicht implementiert |
| 13 | 11005 | 1 | Current SoC | UINT16 | R | RW | % | State of charge | Nicht implementiert |
| 14 | 11006 | 1 | Current DoD | UINT16 | R | RW | % | Depth of discharge | Nicht implementiert |
| 15 | 11007 | 1 | Current SoH | UINT16 | R | RW | % | Aktueller Gesundheitszustand der Batterie (100% = Neu) | Nicht implementiert |
| 16 | 11008 | 2 | Charge Capacity | UINT32 | R | RW | Ah | Ladekapazität in Amperestunden in abhängigkeit der aktuellen Ladeleistung | Nicht implementiert |
| 17 | 11010 | 2 | Energy Capacity | UINT32 | R | RW | Wh | Energiekapazität in Wattstunden in abhängigkeit der aktuellen Ladeleistung | Nicht implementiert |
| 18 | 11012 | 2 | Max Charging Active Power | UINT32 | R | RW | W | Maximale zulässige Ladeleistung | |
| 19 | 11014 | 2 | Max Discharging Active Power | UINT32 | R | RW | W | Maximal zulässige Entladeleistung | |
| 20 | 11016 | 2 | Max Available Inductive Reactive Power | UINT32 | R | RW | var | Maximal zulässige induktive Blindleistung | |
| 21 | 11018 | 2 | Max Available Capacitive Reactive Power | UINT32 | R | RW | var | Maximal zulässige kapazitive Blindleistung | |
| 22 | 11020 | 2 | Charged energy | UINT32 | R | RW | Wh | Geladene Energie | |
| 23 | 11022 | 2 | Available energy | UINT32 | R | RW | Wh | Maximal verfügbare Energie | Nicht implementiert |
| 24 | 11024 | 2 | Total AC Current Phase 1 | INT32 | R | RW | A | AC Summenstrom aller Umrichter für Phase 1 | |
| 25 | 11026 | 2 | Total AC Current Phase 2 | INT32 | R | RW | A | AC Summenstrom aller Umrichter für Phase 2 | |
| 26 | 11028 | 2 | Total AC Current Phase 3 | INT32 | R | RW | A | AC Summenstrom aller Umrichter für Phase 3 | |
| 27 | 11030 | 2 | Setpoint Active Power Mirror | INT32 | R | RW | W | Von 'Setpoint Active Power' empfangener, umkopierter Wert | |
| 28 | 11032 | 2 | Setpoint CosPhi Mirror | FLOAT32 | R | RW | Von 'Setpoint CosPhi' empfangener, umkopierter Wert | ||
| 29 | 11034 | 2 | Current Active Power | INT32 | R | RW | W | Aktuelle Wirkleistung der Gesamtbatterie. Ein positiver Wert bedeutet, dass die Batterie Entladen wird. Ein negativer, dass die Batterie geladen wird. | |
| 30 | 11036 | 2 | Current Reactive Power | INT32 | R | RW | var | Aktuelle Blindleistung der Gesamtbatterie. Ein positiver Wert steht für induktive und ein negativer für Kapazitive Blindleistung | |
| 31 | 11038 | 2 | Life Message | UINT32 | R | RW | Lebenszeichen vom BMS. Wird jeden aktiven Kommunikationszyklus über die Modbus-Schnittstelle inkrementiert. Kann zur Erkennung von Kommunikationsausfällen genutzt werden. | ||
| 32 | 11040 | 4 | Warning Bitmap | BITMAP | R | RW | Bitmaske mit Warnung | Obsolet | |
| 33 | 11044 | 4 | Error Bitmap | BITMAP | R | RW | Bitmaske mit Fehlern | Obsolet | |
| 34 | 12000 | 2 | Setpoint Active Power | INT32 | RW | R | W | Leistungsvorgabe des EMS an das BMS. Negative Leistungsvorgabe zum Laden der Batterie und positive zum Entladen | |
| 35 | 12002 | 2 | Setpoint CosPhi | FLOAT32 | RW | R | Blindleistungsvorgabe des EMS an das BMS per CosPhi | Nicht implementiert, da keine Blidleistung erlaubt ist | |
| 36 | 12004 | 1 | Reactive Power Type | ENUM16 | RW | R | Gibt vor, welche Art von Blindleistung, 'Induktiv', 'Kapaziziv' oder 'Keine' vom BMS eingestellt werden soll | Nicht implementiert, da keine Blidleistung erlaubt ist |