Matthias Heisig
2f9f4df261 changes during start of safety check
- Refactoring of string fb
- Added pump safety interlocks for pressure segment inlet too low and too high
2025-06-02 19:51:57 +02:00
Matthias Heisig
1677d34d9c Added Kaco inverter for sensor ripple testing
- Iso error in string will now only be active if the dc circuit breaker is not closed
- Added some delay between closing dc circuit breaker and enabling inverter so that the dc bus voltage can stabilize itself
2025-05-08 10:07:16 +02:00
Matthias Heisig
0db1fa523a Sunspec heartbeat timer incrementation slowed down 2025-04-28 17:14:43 +02:00
Matthias Heisig
7b810b19d2 Implemented a better balancing algorith for string balancing
* Added error logging to inverter fb
* Changed HMI actual power feedback from dc to ac power
* Small config adjustments
2025-04-16 12:35:06 +02:00
Matthias Heisig
bbf60864db Added inverter active signal to avoid triggering the isolation monitoring 2025-04-15 13:22:55 +02:00
Matthias Heisig
f79cf27c0c Finished first implementation of modbus error registers 2025-04-14 19:38:17 +02:00
Matthias Heisig
2221f6bab3 Minor bugfixes and future addons 2025-04-06 10:21:01 +02:00
Matthias Heisig
2ded890dd4 Added multi string handling and balancing 2025-02-13 21:26:50 +01:00
Matthias Heisig
0345f57a3f Some refactoring 2025-01-17 08:08:37 +01:00
Matthias Heisig
3d041c50c4 - Added new module status
- Added error messages for EtherCAT connection lost
2024-09-05 18:32:49 +02:00
Matthias Heisig
0d9a4d9c72 WIP: Aktueller stand für fehlersuche Sensorrauschen 2024-05-22 17:43:26 +02:00
Matthias Heisig
5c42d4db0a Added ac phase currents to inverter data and copy it to modbus interface 2024-05-07 17:34:01 +02:00
Matthias Heisig
0ffff9be2a EMS communication and Voltage optimizations
- Added data for EMS communication
- Added highest segment voltage for charging check
- Added lowest segment voltage for discharging check
2024-05-07 17:10:29 +02:00
Matthias Heisig
327f324be8 Implemented fixes and improvements during comissioning
- New Balancing mode
- HMI Interface for Inverterdata implemented
- Adjusted GVL_CONFIG values
- Read inverter data even when inverter is off
- Added OPC UA settings to inverter data hmi interface
- Added multisettings to safety project for strings
2024-05-06 11:05:33 +02:00
Matthias Heisig
b95033a155 First string implemented 2024-04-18 08:32:21 +02:00
Matthias Heisig
ef26159a4f Added safety program pre comissioning and started implementing different modes 2024-03-20 18:08:57 +01:00
Matthias Heisig
57987cb19f Fixed Modbus register access 2024-01-17 11:26:11 +01:00
Matthias Heisig
4586e72a0e Added inverter implementation 2024-01-05 16:27:39 +01:00
Matthias Heisig
faa33db290 Projektdateien hinzufügen. 2024-01-04 15:15:26 +01:00