Matthias Heisig
7c462c9cd4
Added Kaco cyclic data exchange change
...
- Power will now only be written if the requested power changed
2025-09-10 08:49:21 +02:00
Markus.Neukirch
39a206a1df
Fixed startup time reset error in balancing mode
2025-09-09 12:28:22 +02:00
Markus.Neukirch
755da644bc
changed modbus communication
...
moved from all requests at the same time to one request after each other through state machine
2025-09-05 16:20:36 +02:00
Markus.Neukirch
f0e6143997
IBN changes
...
added sync units for cabinet temperature, changes in modbus interface to EMS (1.0.4 and 1.0.5), added error counter to modbus communication, lot of changes to kaco (faults, consecutive errors, bms error messages), isolation error ledge, allowed startbalancing when on shutdown, tower light integration
2025-09-05 14:24:37 +02:00
Markus.Neukirch
69749409a3
EStop Changes (added cage door estops)
2025-08-20 15:01:26 +02:00
Matthias Heisig
9c6e28b83d
Added Kaco inverter implementation
...
- Added Kaco inverter implementation
- Small refactoring
- Added release inverter power signal for simultaneous start of the
inverters
2025-08-11 23:26:40 +09:00
Markus Neukirch
6f357a3913
Merge branch 'develop' of gitlab.cmblu.net:sps-allgemein/uniblu into develop
...
# Conflicts:
# PLC/PLC.tmc
# Uniper.tsproj
2025-08-04 18:15:08 +02:00
Markus Neukirch
e2a44b0d37
Added cabinet temperature and modbus registers
...
added cabinet temperature to each module, scs and bms cabinet, added corresponding config, hmi interface, hardware & links. Added corresponding warning bits to modbus registers
2025-08-04 18:10:15 +02:00
Markus Neukirch
dacce53625
Balancing quick fixes
...
allowed operating mode to be change when balancing is started, added lock mechanism to not leave balancing state when not enabled
2025-07-31 14:04:30 +02:00
Markus Neukirch
ee3367eaec
EMS-BMS heartbeat and modbus fixes
...
added ledge and error state when modbus communication is lost, seperated register 13004 (confirm) from registers 13000-13001 (BMS/String warning/error messages) for modbus mapping, added Heartbeat error message to bmsErrors
2025-07-14 18:02:33 +02:00
Matthias Heisig
e6802b87b4
Changes after BMS EMS connection test with uniper
...
- Added EMS heartbeat timeout
- Removed commented code
- Fixed BMS Error DC-Switch: Was true when switch was ok and vice versa
2025-06-19 19:10:26 +02:00
Matthias Heisig
b6791f7951
Small changes after FAT and EMS Test
...
- Changed Modbus server config for EMS connectivity
- Changed some default EWL Limits
2025-06-13 16:37:14 +02:00
Matthias Heisig
6fe10cc58c
Added Doppelhoeckertest
2025-06-10 21:04:06 +02:00
Matthias Heisig
58f3c751d3
Some fixes before the FAT
...
- Refactored inverter Heartbeat check
- Added SafetyComError on EtherCAT checking
- Adjusted lower pressure value for safety plc from 200 mBar to 300mBar
2025-06-06 19:09:12 +02:00
Matthias Heisig
38f44128d1
Added precharge mode
2025-06-04 19:37:25 +02:00
Matthias Heisig
f12063e294
Added some fixed during pre safety check
...
- Fixed bug that SafetyIntlkTimeout could not be acknowledged
- Pumps now dont shut off during error in unit (except over- or underpressure), setpoint is now set to discharge power
- Fixed bug not able to restart safety-check when not all strings where off
- Adjusted Safetyparameters to match safetycheck protocol
2025-06-03 18:02:19 +02:00
Matthias Heisig
2f9f4df261
changes during start of safety check
...
- Refactoring of string fb
- Added pump safety interlocks for pressure segment inlet too low and too high
2025-06-02 19:51:57 +02:00
Matthias Heisig
1677d34d9c
Added Kaco inverter for sensor ripple testing
...
- Iso error in string will now only be active if the dc circuit breaker is not closed
- Added some delay between closing dc circuit breaker and enabling inverter so that the dc bus voltage can stabilize itself
2025-05-08 10:07:16 +02:00
Matthias Heisig
94381dc704
Changed Safety program so that every group can be deactivated
2025-04-28 17:15:43 +02:00
Matthias Heisig
7b810b19d2
Implemented a better balancing algorith for string balancing
...
* Added error logging to inverter fb
* Changed HMI actual power feedback from dc to ac power
* Small config adjustments
2025-04-16 12:35:06 +02:00
Matthias Heisig
390b831286
Hardware reset button now triggers an alarm acknowledge signal
2025-04-14 19:46:02 +02:00
Matthias Heisig
f79cf27c0c
Finished first implementation of modbus error registers
2025-04-14 19:38:17 +02:00
Matthias Heisig
2221f6bab3
Minor bugfixes and future addons
2025-04-06 10:21:01 +02:00
Matthias Heisig
84e0e174a1
Fixed missing multistring handling in some modes
2025-02-14 16:14:07 +01:00
Matthias Heisig
4f0905d64a
Fixed some bugs in cycling mode
2025-02-14 15:42:27 +01:00
Matthias Heisig
2ded890dd4
Added multi string handling and balancing
2025-02-13 21:26:50 +01:00
Matthias Heisig
f9df0a5180
Added precharging to SafetyCheck
2025-02-10 08:44:52 +01:00
Matthias Heisig
0345f57a3f
Some refactoring
2025-01-17 08:08:37 +01:00
Matthias Heisig
39a02352f6
Iso and leackage error messages added
2024-09-10 16:54:17 +02:00
Matthias Heisig
d9f39953a0
Added shutdown when inverter error
2024-09-06 18:47:03 +02:00
Matthias Heisig
3d041c50c4
- Added new module status
...
- Added error messages for EtherCAT connection lost
2024-09-05 18:32:49 +02:00
Matthias Heisig
5e94ba4868
Merge branch 'feature/ManualModeSwitch' into develop
...
# Conflicts:
# PLC/PLC.tmc
# PLC/POUs/FB_String.TcPOU
# PLC/POUs/MAIN.TcPOU
# Uniper.tsproj
2024-08-30 14:32:11 +02:00
Matthias Heisig
08d2ffd136
Added string startup timeout
2024-08-30 13:12:42 +02:00
Matthias Heisig
112f7cb7d9
Added automatic manual mode change for all components if manual mode is selected, Added moving average filter to analog data
2024-08-26 22:19:29 +02:00
Matthias Heisig
58e511438e
Umstellung auf TwinCAT 4026
2024-07-29 07:33:50 +02:00
Matthias Heisig
0d9a4d9c72
WIP: Aktueller stand für fehlersuche Sensorrauschen
2024-05-22 17:43:26 +02:00
Matthias Heisig
cf0d144987
Reordered Modbus registers for Energielenker
2024-05-07 18:02:07 +02:00
Matthias Heisig
5c42d4db0a
Added ac phase currents to inverter data and copy it to modbus interface
2024-05-07 17:34:01 +02:00
Matthias Heisig
0ffff9be2a
EMS communication and Voltage optimizations
...
- Added data for EMS communication
- Added highest segment voltage for charging check
- Added lowest segment voltage for discharging check
2024-05-07 17:10:29 +02:00
Matthias Heisig
327f324be8
Implemented fixes and improvements during comissioning
...
- New Balancing mode
- HMI Interface for Inverterdata implemented
- Adjusted GVL_CONFIG values
- Read inverter data even when inverter is off
- Added OPC UA settings to inverter data hmi interface
- Added multisettings to safety project for strings
2024-05-06 11:05:33 +02:00
Matthias Heisig
b95033a155
First string implemented
2024-04-18 08:32:21 +02:00
Matthias Heisig
9ce3522a70
WIP: Inbetriebnahme vorladen
2024-04-11 19:06:45 +02:00
Matthias Heisig
ef26159a4f
Added safety program pre comissioning and started implementing different modes
2024-03-20 18:08:57 +01:00
Matthias Heisig
57987cb19f
Fixed Modbus register access
2024-01-17 11:26:11 +01:00
Matthias Heisig
4586e72a0e
Added inverter implementation
2024-01-05 16:27:39 +01:00
Matthias Heisig
bd0bbd9c8b
Added Simulation plc and removed unnecessary files from repository
2024-01-04 18:39:55 +01:00
Matthias Heisig
faa33db290
Projektdateien hinzufügen.
2024-01-04 15:15:26 +01:00